Inspections for the day of: Friday, March 9, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-00904 Electrical Rough-In3/9/20183/9/20183/9/2018 3:17:36 PMPPASS
Paul Shreve''s is contact on this job site at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
TI located just inside S2 curtis entrance. Discussed GFCI protection required. Due to number of cooking appliances for permanant previsions for cooking all receptacles located behind serving counter are part of a commercial kitchen and shall have GFCI protection and any other with in 6' of a sink. Wall and underground rough in ok cover
ELE17-02919 Final3/9/20183/9/20183/9/2018 2:42:39 PMPPASS
Lock outs are in place, owners contractor is making the outlets in the room where the load center is located accessible for final testing! I am in Meridian so if I could get a call i''m about 30 min away to meet up! Thx. Steve BPL Phone #: ###-#### Inspection requested via web by Steven Meredith Final ok
ELE18-00908 Electrical Rough-In3/9/20183/9/20183/9/2018 2:11:49 PMPFAIL
Call when you are on your way- Lou Ann Phone #: ###-####
210.52(D)- Bathroom receptacles shall be on a dedicated 20 amp circuit. Exception allows bath lighting to be on same circuit if circuit does not leave bathroom and all wiring would be on 20 amp branch circuit and 12 ga. wire to all. Bath receptacle fed with 12 ga but 14 ga leaves box.
Conference required to discuss.
ELE18-00858 Permanent Service3/6/20183/9/20183/9/2018 1:40:08 PMPPASS
** RE-ENERGIZE Inspection Request ** Power will be shut @10AM with restoration @ 2,3 PM. Please contract Barry (Electrician) @ ###-#### if you have any questions. Thank you. Inspection requested via web by Rob Maes
Discussed overhead service conductors clearance around hot tub. As stated in 680. (A) and (C) conductor outside waters edge and more than 10' from inside edge of tub. p/s o/h rec ok
ELE18-00802 Final3/7/20183/9/20183/9/2018 1:09:37 PMPNR
Please call Kurtis with any questions.
Thanks
###-#### Phone #: ###-#### Inspection requested via web by Christy Cheney
At time of inspection subpanels not set.
ELE18-00802 Permanent Service3/9/20183/9/20183/9/2018 1:09:27 PMPPASS
Please call Kurtis with any questions.
Thanks
###-#### Phone #: ###-#### Inspection requested via web by Christy Cheney p/s o/h rec ok
ELE17-04048 Final3/8/20183/9/20183/9/2018 11:05:46 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
ELE17-03968 Final3/8/20183/9/20183/9/2018 10:44:53 AMAFAIL
2824 garage code
Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.3- Garage GFCI to left of panel shows open ground when tested.
210.23(A)(2)- Appliances fastened in place that exceed 50% of branch circuit shall be fed by a dedicated circuit. Microwave 1460 watts exceeds 50% of 20 amp branch circuit. Remove hood from circuit.
410.16(C)(1)- Incandescent or LED surface mount luminaires shall clear storage shelf by 12" minimum in master clothes closet.
ELE18-00893 Rough-In Permanent Service3/8/20183/9/20183/9/2018 9:57:59 AMAFAIL
Phone #: ###-#### Inspection requested via web by caleb Larson
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage by nail plates.
356.28- Flexible non metallic conduit cut ends shall be trimmed.
422.10- Furnace. Manufacturers instructions state 12 ga. branch circuit conductors minimum shall feed furnace.
ELE18-00864 Temporary Service3/8/20183/9/20183/9/2018 9:14:09 AMACANC
Phone #: ###-#### Inspection requested via web by Alan Lusk
Duplicate request
ELE18-00864 Temporary Service3/8/20183/9/20183/9/2018 9:13:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
t/s u/g n ok
ELE18-00884 Temporary Service3/8/20183/9/20183/9/2018 8:43:16 AMAPASS
This is for temp service. If you have any questions please feel free to contact Jake ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan t/s o/h n ok