ELE20-00078
| Final | 3/9/2020 | 3/9/2020 | 3/9/2020 2:44:33 PM | P | FAIL |
|
|
The dugout project at Bishop Kelly is ready for final inspection. Please call Pat on your way to the appointment ###-####. Phone #: ###-#### Inspection requested via web by Joe McLean 406.9 Receps intalled in damp locations shall be type"WR" (USB type recep in home team dug out) 314.25 All boxes shall have covers (Missing 4sq blank lighting pull box home team storage area)
|
ELE20-00626
| Electrical Rough-In | 3/9/2020 | 3/9/2020 | 3/9/2020 2:08:35 PM | P | FAIL |
|
|
West side wall rough-in. Thanks Phone #: ###-#### Inspection requested via web by Brad Hoots Prints onsite are not stamped set. 330.12 MC shall not be exposed to physical damage. (New wall behind IT room, MC strapped in inside channel of steel stud)
|
ELE20-00804
| Electrical Rough-In | 3/9/2020 | 3/9/2020 | 3/9/2020 1:42:32 PM | P | NH |
|
|
Please contact Butch Gale with any questions.
Thank you ; have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL No access re-call
|
ELE20-00754
| Rough-In Permanent Service | 3/3/2020 | 3/9/2020 | 3/9/2020 1:30:57 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Same Electric Grounding complete. Contractor was installing service entrance conductors. Guy wire kit onsite. p/s o/h rec ok
|
ELE19-04676
| Final | 3/9/2020 | 3/9/2020 | 3/9/2020 12:59:40 PM | P | PASS |
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard Final ok
|
ELE20-00202
| Final | 3/8/2020 | 3/9/2020 | 3/9/2020 10:09:12 AM | A | FAIL |
|
|
The homeowner has stated that he will be home Monday morning. Please let me know if you have any questions. Thank you! Phone #: ###-#### Inspection requested via web by Dan Jennings 110.3B Jacketed MC shall terminate in a listed connector. (Mini split)
|
ELE19-03991
| Final | 3/6/2020 | 3/9/2020 | 3/9/2020 9:49:37 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk 210.52C1 Countertop or similar work surfaces in pantry. (Receps needed in pantry)
|
ELE20-00787
| Electrical Rough-In | 3/6/2020 | 3/9/2020 | 3/9/2020 9:05:17 AM | A | PASS |
|
|
Please contact Mike at the number listed for entry into inspection area Phone #: ###-#### Inspection requested via web by Tye Thomas Underground for generator ok to cover
|
ELE20-00794
| Electrical Rough-In | 3/6/2020 | 3/9/2020 | 3/9/2020 7:14:16 AM | A | CANC |
|
|
Please give me half an hour notice before inspection to insure access. Thank you Shaun ###-#### Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman Inspection cancelled from web by: Shaun Kirkman
|