FIR04-00062
| INSP-Final Inspection | 3/31/2004 | 4/1/2004 | 4/1/2004 12:00:00 AM | A | FAIL |
|
|
This is Grants cell Have a great day!; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Need approved plans 4/1/2004 12:35:09 PM
|
FIR04-00148
| INSP-Sprinkler Rough-in | 3/31/2004 | 4/1/2004 | 4/1/2004 12:00:00 AM | A | FAIL |
|
|
Jeff; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Overspaced in lab cutting area; freezer/cooler need dry pendants; kicthen/deli requires head at bread oven; beam clamps need straps throughout the permited area 4/1/2004 10:15:08 AM
|
BLD02-00369
| FIRE-Final Inspection | 3/31/2004 | 4/1/2004 | 4/1/2004 12:00:00 AM | A | PASS |
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Barbara Moore All items corrected; final okay 4/1/2004 8:34:46 AM
|
FIR03-00159
| INSP-Final Inspection | 4/1/2004 | 4/1/2004 | 4/1/2004 12:00:00 AM | A | PASS |
|
|
All items corrected; final okay 4/1/2004 8:31:42 AM
|
BLD03-02811
| FIRE-Final Inspection | 4/1/2004 | 4/1/2004 | 4/1/2004 12:00:00 AM | P | PART |
|
|
wayne; Phone #: ###-#### Internet Inspection Request from: Darla Downs okay to use second floor restrooms 4/1/2004 3:44:42 PM
|
FIR03-00613
| INSP-Conference | 4/1/2004 | 4/1/2004 | 3/30/2004 12:00:00 AM | A | PART |
|
|
Stop work order issued on fire alarm system in basement; given to Mike Wilson of Turner-McAlvain
|