Inspections for the day of: Thursday, April 1, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00164 INSP-Sprinkler Rough-in3/30/20044/1/20044/1/2004 9:00:21 AMPCANC
Contact Mike - Cover Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
FIR04-00199 INSP-Final Inspection3/31/20044/1/20044/1/2004 12:00:00 AMACANC
contractor wanted to cancel due to card reader problem 4/1/2004 12:11:41 PM
BLD04-00134 FIRE-Final Inspection3/31/20044/1/20044/1/2004 12:00:00 AMAFAIL
provide additional exit sign per plans. install ceiling tile at sprinkler pendants. mount and tag fire extinguishers. track mounted light fixtures have potential to block sprinkler coverage in three locations. if fixtures are moved next to sprinklers, extended canopies are recommended if this is the case 4/1/2004 12:16:36 PM
FIR04-00154 INSP-Sprinkler Rough-in4/1/20044/1/20044/1/2004 12:00:00 AMPPASS
display areas at front of tenant space are ok to cover. I left correction notice with the general contractor about separation requirement between the stockroom and the concealed area above the retail ceiling 4/1/2004 4:25:42 PM
BLD04-00259 FIRE-Conference4/1/20044/1/20044/1/2004 12:00:00 AMPDONE
Contractor wanted a temporary occupancy in a one of the tenant areas. I said no due to outstanding life safety issues which included door hardware, overspaced sprinkler pendants, lack of fire extinguishers and emergency lighting in egress corridors 4/1/2004 4:28:44 PM