FIR04-00164
| INSP-Sprinkler Rough-in | 3/30/2004 | 4/1/2004 | 4/1/2004 9:00:21 AM | P | CANC |
|
|
Contact Mike - Cover Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
FIR04-00199
| INSP-Final Inspection | 3/31/2004 | 4/1/2004 | 4/1/2004 12:00:00 AM | A | CANC |
|
|
contractor wanted to cancel due to card reader problem 4/1/2004 12:11:41 PM
|
BLD04-00134
| FIRE-Final Inspection | 3/31/2004 | 4/1/2004 | 4/1/2004 12:00:00 AM | A | FAIL |
|
|
provide additional exit sign per plans. install ceiling tile at sprinkler pendants. mount and tag fire extinguishers. track mounted light fixtures have potential to block sprinkler coverage in three locations. if fixtures are moved next to sprinklers, extended canopies are recommended if this is the case 4/1/2004 12:16:36 PM
|
FIR04-00154
| INSP-Sprinkler Rough-in | 4/1/2004 | 4/1/2004 | 4/1/2004 12:00:00 AM | P | PASS |
|
|
display areas at front of tenant space are ok to cover. I left correction notice with the general contractor about separation requirement between the stockroom and the concealed area above the retail ceiling 4/1/2004 4:25:42 PM
|
BLD04-00259
| FIRE-Conference | 4/1/2004 | 4/1/2004 | 4/1/2004 12:00:00 AM | P | DONE |
|
|
Contractor wanted a temporary occupancy in a one of the tenant areas. I said no due to outstanding life safety issues which included door hardware, overspaced sprinkler pendants, lack of fire extinguishers and emergency lighting in egress corridors 4/1/2004 4:28:44 PM
|