Inspections for the day of: Friday, April 1, 2005.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-01743 ELE-Aging Inspection4/1/20054/1/20054/1/2005 12:00:00 AM CANC
no response 4/1/2005 4:42:19 PM
ELE04-01825 ELE-Aging Inspection4/1/20054/1/20054/1/2005 12:00:00 AM PART
WSUC 4/1/2005 2:51:16 PM
ELE05-01016 Final4/1/20054/1/20054/1/2005 12:00:00 AMANR
called 4/1/2005 8:47:05 AM
ELE05-00834 Final4/1/20054/1/20054/1/2005 12:00:00 AMAPASS
ELE05-00487 Final4/1/20054/1/20054/1/2005 12:00:00 AMACANC
ELE05-00554 Electrical Rough-In3/31/20054/1/20054/1/2005 12:00:00 AMAPASS
Please contact Duane prior to inspection for specific site location, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters walls and ceilinghs ok 4/1/2005 10:10:22 AM
ELE05-01067 Final3/31/20054/1/20054/1/2005 12:00:00 AMAPASS
paul ###-#### ok 4/1/2005 8:40:44 AM
ELE05-00005 Final3/31/20054/1/20054/1/2005 12:00:00 AMAFAIL
aaron; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie cor closet lights 4/1/2005 8:20:38 AM
ELE05-00004 Final3/31/20054/1/20054/1/2005 12:00:00 AMAFAIL
aaron; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie cor closet lights called
4/1/2005 8:20:09 AM
ELE05-00464 Final3/31/20054/1/20054/1/2005 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 3/31/2005 at 6:23:57 PM. Contact: ###-####. electrical ok cannot final cor posted on bld04-01780 for phone and alarm contractor, remove phone cable from below panels told 1 month ago, provide bushings for alarm at raceways and where it enterx door and window frames used as raceways told him 4 days ago 4/1/2005 12:19:10 PM
ELE05-00500 Permanent Service3/31/20054/1/20054/1/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 3/31/2005 at 10:27:17 PM. p/s u/g rec. ok see added r/i 4/1/2005 9:31:48 AM
ELE05-00500 Electrical Rough-In4/1/20054/1/20054/1/2005 12:00:00 AMAFAIL
cor. posted for service at in basement BBC no violations to be retained panel was install without permit or inspection all messed up clearence problems , shall be brought up to current NEC, also electrical contractor disconnected wiring to new spa, spa shall not be used until all wiring is complete and meets requirements of art 680
ELE05-01041 Electrical Rough-In4/1/20054/1/20054/1/2005 12:00:00 AMPPASS
dennis ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 4/1/2005 1:49:59 PM
ELE05-00141 Final4/1/20054/1/20054/1/2005 12:00:00 AMPPASS
per jack frank--john ###-#### okcard signed 4/1/2005 1:16:58 PM
ELE04-03671 Electrical Rough-In4/1/20054/1/20054/1/2005 12:00:00 AMPPART
cord not allowed for track lighting
ELE05-01041 Permanent Service4/1/20054/1/20054/1/2005 12:00:00 AMPPASS
p/s o/h new ok
ELE03-01602 Electrical Rough-In3/14/20054/1/20054/1/2005 12:00:00 AMPFAIL
###-#### - henry cor. do not cover posted met owner,210.52(A) outlet spacing 210.52(D) 20 bath circuit, 300.4 nail 11/4", 314.16 box fill 4/1/2005 3:14:17 PM
ELE05-00459 Electrical Rough-In4/1/20054/1/20054/1/2005 12:00:00 AMPNR
henry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore lots of things wrong called contractor, he will reschedule inspection and meet me for conference 4/1/2005 3:52:23 PM