Inspections for the day of: Friday, April 1, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00564 Final3/31/20054/1/20054/1/2005 12:00:00 AMAPASS
george says you scheduled with him for 8:30am; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
ELE05-01089 Final3/31/20054/1/20054/1/2005 12:00:00 AMAFAIL
###-####-- dan
fles arranged to drain
weatherproof box required or garage door 4/1/2005 3:20:53 PM
ELE05-01089 Rough-In Permanent Service3/31/20054/1/20054/1/2005 12:00:00 AMAPASS
dan--###-####
ELE05-01061 Temporary Service3/31/20054/1/20054/1/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 3/31/2005 at 2:23:50 PM. Contact: ###-####.
damaged recep
250.24
408.21 4/1/2005 10:51:43 AM
ELE05-01091 Electrical Rough-In3/31/20054/1/20054/1/2005 12:00:00 AMAPART
underground inspection please///bob ###-####
ELE04-03172 Final3/31/20054/1/20054/1/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 3/31/2005 at 3:20:24 PM. Contact: ###-####.
closet light in master open bulb
receps in dinning room 210.52 4/1/2005 9:53:13 AM
ELE05-01060 Electrical Rough-In3/31/20054/1/20054/1/2005 12:00:00 AMAFAIL
###-#### - shawn
517.13 4/1/2005 9:47:37 AM
ELE05-00894 Permanent Service4/1/20054/1/20054/1/2005 12:00:00 AMAPASS
P/S U/g N Ok 4/1/2005 9:46:58 AM
ELE05-00974 Electrical Rough-In3/31/20054/1/20054/1/2005 12:00:00 AMPFAIL
heather; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
several 2 gang boxes overfilled
210.52
protection of parallel conductors 4/1/2005 3:52:16 PM
ELE04-03891 Electrical Rough-In4/1/20054/1/20054/1/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 4/1/2005 at 9:02:11 AM. Contact: ###-####.
ELE05-00383 Electrical Rough-In4/1/20054/1/20054/1/2005 12:00:00 AMPFAIL
Partial celing cover, please contact Nick, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters
support wires not tight
mc supported from other cable
unused openings in boxes 4/1/2005 2:35:37 PM
ELE05-01037 Permanent Service4/1/20054/1/20054/1/2005 12:00:00 AMPNR
###-#### - heather
must find out if this is 1 or 2 buildings 4/1/2005 1:59:46 PM
ELE05-01090 Temporary Service3/31/20054/1/20054/1/2005 12:00:00 AMPPASS
bob ###-####
T/S O/H Ok 4/1/2005 1:32:04 PM