PLM08-00677
| Plumbing Rough-in | 3/31/2008 | 4/1/2008 | 4/1/2008 4:42:45 PM | P | PASS |
|
|
Please call Landon 30 min before so he can meet you at job. Thanks Phone #: ###-#### Internet Inspection Request from: LANDON ADANK
|
PLM08-00405
| Plumbing Rough-in | 4/1/2008 | 4/1/2008 | 4/1/2008 3:59:32 PM | P | PASS |
|
|
Please call ###-#### a half hour prior to arrival for access to jobsite. Thank you Phone #: ###-#### Internet Inspection Request from: Mike Dunson
|
PLM08-00605
| Water and/or Sewer | 4/1/2008 | 4/1/2008 | 4/1/2008 3:41:56 PM | P | PART |
|
|
6th Floor - Tower Inspection - 6 Rooms Phone #: ###-#### Internet Inspection Request from: Colleen Brown-south side flr 6 pass.
|
PLM08-00674
| Sprinkler (Final) | 3/31/2008 | 4/1/2008 | 4/1/2008 3:24:00 PM | P | PASS |
|
|
Jackie ###-####
|
PLM08-00673
| Other | 4/1/2008 | 4/1/2008 | 4/1/2008 2:42:39 PM | P | PART |
|
|
this is for a walk thru with bill thompson at 1:30 pm-need a dbca for premis, rpba for make up water for boilers needs tested & certified, dishwasher in kitchen needs a rpba, all eyewashes need pvb's, soap dispensors on mop sinks need replaced with one's with air gap or add rpba's. needs done by final. water line from curb up to manafold ok to cover, still needs tested.
|
PLM08-00602
| Plumbing Rough-in | 3/31/2008 | 4/1/2008 | 4/1/2008 10:40:27 AM | A | FAIL |
|
|
lon Phone #: ###-####-vent for bath & ejector need to be relocated or be 6" above flood level rim of upstairs powder bath sink, check valve & ball valve for ejector installed in wrong order, no test on dwv. contractor will call daryl to see what he will require for test.
|
PLM08-00673
| Plumbing Rough-in | 3/31/2008 | 4/1/2008 | 4/1/2008 9:58:34 AM | A | PART |
|
|
rough in ready Tues. AM Phone #: ###-#### Internet Inspection Request from: Bonnie Gilbert-sewer pass.
|
PLM08-00605
| Water and/or Sewer | 3/31/2008 | 4/1/2008 | 4/1/2008 9:56:32 AM | A | PART |
|
|
3rd and 4th floor tower inspection Phone #: ###-#### Internet Inspection Request from: Colleen Brown-3rd & 4th flr pass.
|
PLM08-00663
| Water and/or Sewer | 3/31/2008 | 4/1/2008 | 4/1/2008 8:35:13 AM | A | PASS |
|
|
If you have any questions, please call Mike @ ###-####. Thank you for your time. Maggie Abrao Plumbing Phone #: ###-#### Internet Inspection Request from: Michael Abrao
|
PLM08-00663
| DOC - Permit Finaled | 4/1/2008 | 4/1/2008 | 4/1/2008 8:35:02 AM | P | PASS |
|
|
If you have any questions, please call Mike @ ###-####. Thank you for your time. Maggie Abrao Plumbing Phone #: ###-#### Internet Inspection Request from: Michael Abrao
|
PLM06-04019
| PLM-Aging Inspection | 4/1/2008 | 4/1/2008 | 4/1/2008 8:28:41 AM | | PASS |
|
|
|