Inspections for the day of: Wednesday, April 1, 2009.
Number of inspections: 13
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00255 INSP-Final Inspection3/27/20093/27/2009 P 
Contact Rafe Phone#: ###-####
BLD06-02303 FIRE-Hydro test above ground4/1/20094/1/20094/2/2009 2:08:45 PMPPART
Hydrostatic retesting for the 14th floor completed, concluded satisfactory 24 hr. air test for the 3rd and 4th floor dry systems.
BLD09-00396 FIRE-Final Inspection4/1/20094/1/20094/1/2009 4:13:13 PMPPASS
Need to provide approved hardware at the back exit door or blank the exit sign prior to structural final approval.
BLD09-00074 FIRE-Final Inspection4/1/20094/1/20094/1/2009 4:07:36 PMPPASS
Fire life safety inspection completed acceptable.
FIR09-00143 INSP-Final Inspection4/1/20094/1/20094/1/2009 3:29:24 PMPPASS
Scope of fire sprinkler work passed inspection, field mods. okayed, permit finaled.
FIR08-00766 INSP-Sprinkler Rough-in/Hydro3/31/20094/1/20094/1/2009 3:04:04 PMPPART
Hydrostatic testing for UG supply lead in piping service to the truck return and maintenance buildings each completed satisfactory, maint. building service okayed within allowable leakage amounts per NFPA 13.
FIR08-00366 INSP-Final Inspection3/31/20094/1/20094/1/2009 2:59:21 PMANR
Need to provide reset key to facilitate elevator recall testing, discussed firemans hat illumination per review comments.
BLD09-00301 FIRE-Final Inspection3/31/20094/1/20094/1/2009 12:53:28 PMAPART
See red-lines on plans for rack installation okayed to date.
BLD09-00074 FIRE-Final Inspection3/31/20094/1/20094/1/2009 12:43:20 PMANR
Project related fire sprinkler permit work is not ready for final, noted one overspaced head at the kitchen area due to relocated wall. Remainder of life safety items inspected okayed including fire alarm and type one hood.
FIR09-00140 INSP-Final Inspection4/1/20094/1/20094/1/2009 12:40:18 PMPPASS
Scope of fire alarm work passed field testing, permit finaled.
FIR09-00118 INSP-Final Inspection3/31/20094/1/20094/1/2009 12:39:10 PMAPASS
Hood suppression system operated correctly under test conditions.
FIR08-00834 FIR-Aging Inspection4/1/20094/1/20094/1/2009 10:57:06 AM DONE
Work in progress, construction underway.
FIR09-00140 INSP-Alarm Testing3/31/20094/1/20094/1/2009 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 3/31/2009 at 11:31:58 AM. Contact: ###-####.