Inspections for the day of: Thursday, April 1, 2010.
Number of inspections: 12
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00694 INSP-Final Inspection3/30/20103/30/2010 P 
Robert Phone #: ###-####
FIR03-00362 DOC - Permit Expired4/1/20104/1/20104/2/2010 4:04:39 PMPPASS
Ref. IFC 2006 105.3.1
FIR03-00363 FIR-Aging Inspection4/1/20104/1/20104/1/2010 5:20:49 PMPDONE
BLD10-00446 FIRE-Final Inspection4/1/20104/1/20104/1/2010 5:19:55 PMPPASS
Life safety is acceptable pending the fire extinguisher is posted as discussed and approved hardware is provided at the new restroom door- structural inspector to verify at final as agreed.
FIR10-00011 INSP-Sprinkler Rough-in4/1/20104/1/20104/1/2010 5:17:01 PMPPART
Don Phone #: ###-####
FIR09-00327 FIR-Aging Inspection4/1/20104/1/20104/1/2010 5:16:34 PMPDONE
Final scheduled
FIR09-00612 INSP-Final Inspection4/1/20104/1/20104/1/2010 5:15:47 PMPPART
Construction underway
BLD10-00295 FIRE-Conference4/1/20104/1/20104/1/2010 5:14:56 PMADONE
Need to post fire extinguishers per review note comments, no storage allowed to obstruct access at the riser rooms.
BLD10-00296 FIRE-Final Inspection4/1/20104/1/20104/1/2010 5:11:17 PMAPART
Okay pending project attatched FIR permit final approval.
FIR09-00642 INSP-Sprinkler Rough-in4/1/20104/1/20104/1/2010 5:09:23 PMAPART
Completed overhead inspections at all new areas including the dry storage, east and west recieving, cooler #3, vat room, cultured packaging and production and dock. CIP room is not finished at this time, discussed hydrostatic testing schedule, noted a fire alarm permit to include new riser and antifreeze loop monitor points will be necessary. Red lined correction items on stamped plan set (seismic bracing, pend. outlet on dry system, etc.) including field modifications to be indicated on record drawings for relocated main, FDC, new SW heads. Riser needs tagged and head boxes mounted, RP and DCVA tested while on site.
FIR09-00524 INSP-Sprinkler Rough-in4/1/20104/1/20104/1/2010 4:54:22 PMAPASS
FIR10-00055 INSP-Sprinkler Rough-in4/1/20104/1/20104/1/2010 4:53:51 PMAPART
Overhead fire sprinkler work passed rough-in inspection.