Inspections for the day of: Monday, April 1, 2013.
Number of inspections: 12
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS13-00072 FIR-Conference3/27/20133/27/2013 P 
waiting on Stephanie to check documents
FIR13-00086 INSP-Conference4/1/20134/1/20134/2/2013 10:21:31 AMPDONE
I spoke with both the general contractor and the electrician about contacting the fire dept for approval for phasing the project and partial occupancy.
FIR13-00020 INSP-Sprinkler Rough-in/Hydro4/1/20134/1/20134/2/2013 10:18:55 AMPPASS
See the city approved plans for residences that are either rough-in approved or approved for cover.
FIR13-00109 INSP-Supply line flush4/1/20134/1/20134/1/2013 4:04:19 PMPCANC
Not ready for a flush. To be rescheduled.
FIR13-00108 INSP-Supply line flush4/1/20134/1/20134/1/2013 4:00:43 PMPCANC
Not ready for a flush. To be rescheduled.
FIR13-00107 INSP-Supply line flush4/1/20134/1/20134/1/2013 3:15:14 PMPCANC
Not ready for a flush. To be rescheduled.
FIR12-00670 INSP-Sprinkler Rough-in3/28/20134/1/20134/1/2013 2:30:16 PMPPASS
See the city approved plans for two locations marked in red where the hardlid ceilings can be installed. Also the rough-in inspection for the overhead lines passed. Not all of the drops have been installed/piped. I noted two locations where retaining straps are not bent over the truss. Also plan modifications will be needed due to additional elbows in both the 2 1/2" and 4" mains that supply the remote areas.
FIR13-00109 INSP-Sprinkler Rough-in/Hydro4/1/20134/1/20134/1/2013 2:26:19 PMPPASS
This is an ug hydro.
FIR13-00108 INSP-Sprinkler Rough-in/Hydro4/1/20134/1/20134/1/2013 2:25:15 PMPPASS
This is an ug hydro.
FIR13-00107 INSP-Sprinkler Rough-in/Hydro4/1/20134/1/20134/1/2013 2:23:42 PMPPASS
This is an ug hydro.
BLD13-00709 FIRE-Final Inspection3/29/20134/1/20134/1/2013 9:35:30 AMAFAIL
Karen Thomas-Please call at least 30 mins prior to inspection Phone #: ###-####

The contact requested 30 min notice. I left message at 9:00 that I would be there by 9:30. I left business at 9:35 after making no contact. Business is locked with no access.
FIR13-00109 INSP-Supply line flush4/1/20134/1/20134/1/2013 9:02:25 AMPCANC
This is an ug hydro. Dales is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus