MEC19-00468
| Final | 4/1/2019 | 4/1/2019 | 4/1/2019 4:19:50 PM | P | PASS |
|
|
David Phone #: ###-#### - final ok
|
MEC19-00468
| Rough-in | 4/1/2019 | 4/1/2019 | 4/1/2019 3:49:27 PM | P | PASS |
|
|
David Phone #: ###-####
|
MEC19-01271
| Rough-in | 4/1/2019 | 4/1/2019 | 4/1/2019 3:25:02 PM | P | PASS |
|
|
This is a reinspection Call me in case it is locked so you can get the code Phone #: ###-#### Inspection requested via web by marco gomez - R/I ok
|
MEC19-01309
| Rough-in | 4/1/2019 | 4/1/2019 | 4/1/2019 3:13:25 PM | P | NR |
|
|
Ben Phone #: ###-#### - exhaust fan needs flex ducting installed per manufactures spec. Inner liner taped and outer liner zip tied - termination point on roof needs finished. flex attached to j vent on roof per manufactures spec - need to see mini split lineset and condensate roughed in
|
MEC18-04683
| Final | 4/1/2019 | 4/1/2019 | 4/1/2019 2:52:02 PM | P | PART |
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak - temp final ok
|
MEC19-01222
| Rough-in | 4/1/2019 | 4/1/2019 | 4/1/2019 2:51:43 PM | P | PART |
|
|
PART Phone #: ###-#### Inspection requested via web by Oleg Chervak - pre rock cover ok exhausts and linesets ok
|
MEC19-01166
| Final | 3/26/2019 | 4/1/2019 | 4/1/2019 2:51:04 PM | P | PASS |
|
|
installer jarod ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - furnace ac coil co ok
|
MEC19-01161
| Rough-in | 3/28/2019 | 4/1/2019 | 4/1/2019 11:46:20 AM | A | FAIL |
|
|
Call Jason @ ###-#### with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire - water heater flue needs 1" clearances insulation below 2nd floor is touching b vent
|
MEC19-01161
| Pressure Test | 3/28/2019 | 4/1/2019 | 4/1/2019 11:45:25 AM | A | PASS |
|
|
Call Jason @ ###-#### with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire - 5lb flue pressure test ok -20lb gas pressure test ok - tagged meter location
|
MEC18-03323
| Final | 3/29/2019 | 4/1/2019 | 4/1/2019 10:22:38 AM | A | PASS |
|
|
Inspection requested via web by Marisa Hone - A/C coil co ok
|
MEC19-01291
| Final | 3/29/2019 | 4/1/2019 | 4/1/2019 10:07:07 AM | A | PASS |
|
|
FAN INSTALLED Phone #: ###-#### Inspection requested via web by Andrea Creek - final ok - signed occ card
|
MEC19-01025
| Rough-in | 3/29/2019 | 4/1/2019 | 4/1/2019 9:49:16 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Arielle Hendricks - R/I ok
|
MEC19-01025
| Pressure Test | 3/29/2019 | 4/1/2019 | 4/1/2019 9:45:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Arielle Hendricks - 20lb gas pressure test ok - tagged meter location
|
MEC19-01012
| Rough-in | 3/29/2019 | 4/1/2019 | 4/1/2019 9:45:04 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Arielle Hendricks - R/I ok - tagged meter location for pressure test
|
MEC19-00885
| Final | 3/29/2019 | 4/1/2019 | 4/1/2019 9:10:00 AM | A | PASS |
|
|
Please inspect late AM to close out permit. Phone #: ###-#### Inspection requested via web by Arielle Hendricks - final ok
|
MEC19-00925
| Final | 3/29/2019 | 4/1/2019 | 4/1/2019 9:09:16 AM | A | PASS |
|
|
Please inspect late AM.Call Tyrel on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - unit heater final ok
|
MEC18-06136
| Final | 3/29/2019 | 4/1/2019 | 4/1/2019 9:01:22 AM | A | CANC |
|
|
Duct blast witness 10am, thanks Phone #: ###-#### >> Inspection requested via web by Gary Reeves Inspection cancelled from web by: Gary Reeves
|
MEC18-03089
| Final | 3/31/2019 | 4/1/2019 | 4/1/2019 8:55:37 AM | A | PASS |
|
|
Please call Mr. Devore prior to heading out at 208.513.6470. Phone #: ###-#### Inspection requested via web by Andrea Grigsby - A/C coil co ok
|
MEC18-03329
| Mec-Aging Inspection | 4/1/2019 | 4/1/2019 | 4/1/2019 8:39:22 AM | | DONE |
|
|
Called TML and talked with Debbie about their mechanical aging permit. Schedule inspection with homeowner if ready. Permit will expire in 180 days if not active
|
MEC18-03367
| Mec-Aging Inspection | 4/1/2019 | 4/1/2019 | 4/1/2019 8:36:20 AM | | DONE |
|
|
Called Mark the permit holder about his mechanical aging permit on a ductless split. Schedule inspection on ductless split if ready. Permit will expire in 180 days if not active
|
MEC18-05605
| Final | 3/29/2019 | 4/1/2019 | 4/1/2019 8:30:45 AM | A | PASS |
|
|
Ken Phone #: ###-#### - final ok
|
MEC19-01270
| Rough-in | 3/29/2019 | 4/1/2019 | 4/1/2019 8:29:52 AM | A | PASS |
|
|
Manual-j is attached to lineset Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek - R/I ok - tagged meter location
|