Inspections for the day of: Wednesday, April 1, 2020.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01159 Electrical Rough-In4/1/20204/1/20204/1/2020 3:00:02 PMPPASS
This location needs inspected for cover. Please call Paul ###-#### prior to the appointment and he will be on site. Phone #: ###-#### Inspection requested via web by Joe McLean Confirmed a set of city approved prints on site. Show window receptacles required as per 210.62.
Wall rough in ok cover.
ELE20-00308 Electrical Rough-In4/1/20204/1/20204/1/2020 2:37:35 PMPPASS
Please call Ben @ ###-#### prior to arrival to meet on site or to give inspector code to lockbox. Thanks. Phone #: ###-#### Inspection requested via web by Scott Campbell City approved set of prints on site confirmed. Asked to have ELE attached to BLD20-00851. Wall rough in ok cover.
ELE20-00179 Conference4/1/20204/1/20204/1/2020 2:03:47 PMPPASS
John Busnardo (electrician) is the contact. He is needing an on-site meeting to go over electrical devices approved by the electrical engineer prior to installation. Thank you Phone #: ###-#### Inspection requested via web by A.M.E. Office
Discussed the rating of receptacle boxes and covers in the Eastern exposed recessed portion of structure. Receptacle boxes and covers spec'ed out do not have a rating included with discription. Explained all outdoor receptacles are required to be rated for damp and wet locations where exposed to weather or spray as per 406.9. Also receptacles existing without proper covers would need covers installed compliant with todays code.
As per previous conversation about 600+ amps of disconnecting means on 200 amp rated wires would need a main breaker to protect previously installed conductors in gutter. A 200 amp main breaker exists at service location.
ELE19-03884 ELE-Request for Extension4/1/20204/1/20204/1/2020 11:16:18 AMPPASS
NOT AN INSPECTION REQUEST BUT A REQUEST TO EXTEND THIS PERMIT PLEASE. THIS PERMIT EXPIRES ON 4/6/2020 - PLEASE EXTEND. CALL MARIA FOR ANY QUESTION. ###-#### Phone #: ###-####
Inspection requested via web by Kyle Lott
Extension ok
ELE20-00708 Final4/1/20204/1/20204/1/2020 10:59:15 AMAPASS
ceiling grid, call 1/2 hr prior Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Final ok
ELE20-00708 Electrical Rough-In4/1/20204/1/20204/1/2020 10:45:41 AMAPASS
ceiling grid, call 1/2 hr prior Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Grid rough in ok cover
ELE20-01153 Permanent Service3/31/20204/1/20204/1/2020 10:18:30 AMAPASS
200amp service - due to tree Phone #: ###-#### Inspection requested via web by Kendra Lanham p/s o/h rec ok
ELE20-01153 Final4/1/20204/1/20204/1/2020 10:17:57 AMPPASS
200amp service - due to tree Phone #: ###-#### Inspection requested via web by Kendra Lanham Final ok
ELE20-00219 Final3/31/20204/1/20204/1/2020 9:50:32 AMAFAIL
Phone #: ###-#### Inspection requested via web by Emmet Bushman
110.3- 2 receptacle outlets not working in bed off garage.
210.8- Unable to verify GFCI protection on floor heat thermostat due to sensor issue according to instructions.