ELE06-01166
| Electrical Rough-In | 4/10/2006 | 4/10/2006 | 4/10/2006 4:23:11 PM | P | PASS |
|
|
Mike -- reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong walls only ok
|
ELE05-03187
| Final | 4/10/2006 | 4/10/2006 | 4/10/2006 3:59:49 PM | P | PASS |
|
|
Tim; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok
|
ELE05-03919
| Final | 4/10/2006 | 4/10/2006 | 4/10/2006 3:22:23 PM | P | FAIL |
|
|
PLEASE CALL DAVE BRADSHAW & HE WILL MEET THE INSPECTOR @ THE JOBSITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail corr. called 250.8 no SMS allowed for grds or bonds, 310.15 (B)(2) table derate at 50%, 250.122(B) shall increase equip grds also for size, 250.12shall remove paint for clean surface at equip grd bus j box,, 250.126 for equip grd bus at jbox
|
ELE05-04628
| Final | 4/10/2006 | 4/10/2006 | 4/10/2006 2:20:05 PM | P | PASS |
|
|
kent; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE06-00015
| Final | 4/10/2006 | 4/10/2006 | 4/10/2006 2:19:41 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 4/10/2006 at 7:45:00 AM. Contact: ###-####. ok
|
ELE06-00081
| ELE-Aging Inspection | 4/10/2006 | 4/10/2006 | 4/10/2006 1:25:23 PM | | NR |
|
|
no new signs installed yet
|
ELE04-02822
| Final | 4/8/2006 | 4/10/2006 | 4/10/2006 1:24:48 PM | P | PASS |
|
|
final inspection, made corrections on disconnect; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa corr. made
|
ELE06-00422
| Electrical Rough-In | 4/7/2006 | 4/10/2006 | 4/10/2006 9:55:55 AM | A | PART |
|
|
this is for an inspection at the reception area. any questions please call Steve Nuxoll; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok
|
ELE06-00053
| Final | 4/10/2006 | 4/10/2006 | 4/10/2006 8:45:27 AM | A | PASS |
|
|
sign faces changed final ok
|