Inspections for the day of: Monday, April 10, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-00084 FIRE-Final Inspection4/10/20064/10/20064/10/2006 6:37:25 PMPFAIL
Max occupant load sign is not yet posted, approved plans and sign off card not available on site.
FIR05-00875 INSP-Final Inspection4/7/20064/10/20064/10/2006 4:55:42 PMPFAIL
Heads at two locations as marked on approved plans are blocked by surface mounted light obstructions, the elevator shaft has been deleted and divided to form two separate rooms which will require protection per NFPA 13D, witnessed satisfactory UG flush, missing canopy installed while on site.
FIR06-00075 INSP-Sprinkler Rough-in4/10/20064/10/20064/10/2006 4:00:39 PMPDEFR
todd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles No time available for this inspection today, to be rescheduled per conversation with contractor.
FIR05-00449 INSP-Alarm Testing4/7/20064/10/20064/10/2006 3:59:07 PMAPART
Tested detection and notification devices on the 3rd and 4th floors, HVAC units were not in a condition to be tested in the fan rooms, missing mag door holder at the 3rd floor north double doors (door release not verified), checked audibility in the fan room on 2nd floor, previous c/n items are satisfactory, discussed inspection schedule for the remainder of this project with D. Maxwell.
FIR05-00564 INSP-Final Inspection4/7/20064/10/20064/10/2006 2:20:10 PMPPASS
Verified occupancy use in office 102 does not require visual notification, resubmitted plans verified, permit finaled.
BLD04-00949 FIRE-Final Inspection4/10/20064/10/20064/10/2006 2:13:08 PMPFAIL
The project related fire alarm and sprinkler permits must be inspected and approved prior to building life safety final inspection.
FIR05-00853 INSP-Final Inspection4/6/20064/10/20064/10/2006 2:11:17 PMPPASS
Items on correction notice have been completed as required, fire sprinkler finaled.
FIR05-00586 INSP-Sprinkler Rough-in/Hydro4/10/20064/10/20064/10/2006 12:03:36 PMPNR
Per phone conversation with contractor, project is not ready for a hydrostatic test at this time as scheduled.
FIR06-00038 INSP-Final Inspection4/7/20064/10/20064/10/2006 11:54:28 AMAPASS
Fire sprinkler work is satisfactory, permit finaled.
FIR06-00183 INSP-Final Inspection4/7/20064/10/20064/10/2006 11:52:47 AMAPASS
Corrections have been made, modifications tested, signals verified, fire alarm inspection passed.
FIR06-00083 INSP-Final Inspection4/10/20064/10/20064/10/2006 11:33:20 AMPPASS
Inspection completed in the AM as previously agreed, fire alarm functioned properly, inspection passed.
FIR05-00425 INSP-Sprinkler Rough-in/Hydro4/7/20064/10/20064/10/2006 11:03:57 AMAPART
Overhead rough-in inspection for the 6th floor is good for cover at the hard lid areas as discussed, items addressed include missing 4-way EQ brace, blocked ssu at south stair #1, fire caulking not complete in some areas, added lines in guest room soffits must be shown on plan, be aware of possible light fixture and soffit obstructions, some SW heads are not cut in at this time, laundry chute head is not piped.
BLD02-02815 FIRE-Final Inspection4/7/20064/10/20064/10/2006 10:11:28 AMAPASS
Outstanding items have been completed, fire life safety inspection passed.
FIR06-00128 INSP-Sprinkler Rough-in/Hydro4/7/20064/10/20064/10/2006 9:47:20 AMAPART
Overhead rough-in is good for cover at the four restrooms with hard lids on the first floor as marked on plans, no other areas requested for inspection at this time.
FIR05-00804 INSP-Final Inspection4/7/20064/10/20064/10/2006 8:20:44 AMACANC
we are now ready. Could you please call me when you have an approximate time you'll be out. Thanks, Harry ; Phone #: ###-#### Internet Inspection Request from: Harry Thompson Inspection cancelled from web by: Harry Thompson