ESC04-00024
| Site Final | 4/10/2009 | 4/10/2009 | 4/10/2009 4:18:07 PM | P | PASS |
|
|
ok all work complete
|
ESC05-01249
| Site Final | 4/10/2009 | 4/10/2009 | 4/10/2009 4:17:20 PM | P | PASS |
|
|
ok all work complete
|
ESC04-00163
| Site Final | 4/10/2009 | 4/10/2009 | 4/10/2009 4:16:32 PM | P | PASS |
|
|
ok all work complete
|
ESC07-00272
| Site Final | 4/10/2009 | 4/10/2009 | 4/10/2009 4:15:40 PM | P | PASS |
|
|
ok all work complete
|
ELE09-00562
| Electrical Rough-In | 4/6/2009 | 4/10/2009 | 4/10/2009 3:01:01 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
|
ELE09-00562
| Final | 4/10/2009 | 4/10/2009 | 4/10/2009 3:00:53 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
|
ELE07-02834
| Final | 4/7/2009 | 4/10/2009 | 4/10/2009 2:35:32 PM | P | FAIL |
|
|
lars - please call 1/2 hr prior for access Phone #: ###-#### job not ready shall wire spa too meet article 680 of NEC, spa wiring is a complete mess called
|
ELE09-00604
| Permanent Service | 4/10/2009 | 4/10/2009 | 4/10/2009 1:44:11 PM | P | FAIL |
|
|
insp on moving the sub panel//Ron ###-#### see added r/i
|
ELE09-00604
| Electrical Rough-In | 4/10/2009 | 4/10/2009 | 4/10/2009 1:43:49 PM | P | FAIL |
|
|
insp on moving the sub panel//Ron ###-#### 314.28(A)(2) shall provide 6X for raceway entries at jbox, 310.16 shall not use $ copper for 100 amp commercial job,200.6&7 shall not ID 6 or smaller neutral shall be white, shall ID neutral used as phase in cables, 250.148 shall terminate all equip. grds to jbox (old panel)BCC no vilations retained grding and bonding at p/s shall meet article 250, also 110.3(B) manufactures instructions use manufactures listed breakers only called left message
|
ELE08-02167
| Electrical Rough-In | 4/9/2009 | 4/10/2009 | 4/10/2009 11:07:13 AM | A | PART |
|
|
andy Phone #: ###-#### north and east corner ok building ceiling ok only still needs to meet 300.4 (E) for other areas, also 250.122 (B) for pole lights size of equip grd
|
ELE09-00598
| Temporary Service | 4/10/2009 | 4/10/2009 | 4/10/2009 10:23:12 AM | A | PASS |
|
|
t/s u/g new ok
|
ELE09-00598
| Electrical Rough-In | 4/9/2009 | 4/10/2009 | 4/10/2009 10:22:49 AM | A | CANC |
|
|
###-#### Internet Inspection Request from: Todd Holbrook see added t/s
|
ELE09-00300
| Electrical Rough-In | 4/9/2009 | 4/10/2009 | 4/10/2009 9:48:13 AM | A | FAIL |
|
|
please provide rough in inspection for bathroom radient floor heat in main and master bathroom. Call Dave if you have any questions. Phone #: ###-#### Internet Inspection Request from: David Mackey called 110.3(B) shall follow manufactures instructions for installation of floor heat, I marked the sections on instruction sheet, spacing and placement of sensor lead
|
ESC08-00950
| General Inspection | 4/10/2009 | 4/10/2009 | 4/10/2009 9:44:58 AM | A | PASS |
|
|
|
ELE09-00340
| Final | 4/9/2009 | 4/10/2009 | 4/10/2009 8:53:12 AM | A | PASS |
|
|
please final. All underground work is complete and lighting is operational again. Call Dave if you have any questions Phone #: ###-#### Internet Inspection Request from: David Mackey
|
ELE09-00563
| Final | 4/10/2009 | 4/10/2009 | 4/10/2009 8:13:24 AM | A | PASS |
|
|
inspection on service only, power has been off over a year. any questions call Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose
|
ELE09-00563
| Permanent Service | 4/9/2009 | 4/10/2009 | 4/10/2009 8:10:00 AM | A | PASS |
|
|
inspection on service only, power has been off over a year. any questions call Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose p/s u/g rec. okl
|
ELE09-00578
| Final | 4/10/2009 | 4/10/2009 | 4/10/2009 8:09:06 AM | A | PASS |
|
|
|