FIR09-00115
| INSP-Sprinkler Rough-in/Hydro | 4/9/2009 | 4/10/2009 | 4/10/2009 3:55:46 PM | A | PART |
|
|
Need resubmitted plans for modifications at the new lunchroom, mech. room, and elevator pit, noted one missing retaining strap. Missing hanger per previous inspection installed.
|
BLD09-00002
| FIRE-Final Inspection | 4/10/2009 | 4/10/2009 | 4/10/2009 3:53:23 PM | P | NR |
|
|
Project related fire alarm test failed.
|
FIR08-00840
| FIR-Aging Inspection | 4/10/2009 | 4/10/2009 | 4/10/2009 3:52:51 PM | | DONE |
|
|
Work in progress, construction underway.
|
BLD09-00157
| FIRE-Final Inspection | 4/10/2009 | 4/10/2009 | 4/10/2009 3:52:22 PM | P | PASS |
|
|
C/N items completed, exit signs/EM lights tested okay, storage over 12' removed, high piled storage is not allowed per the conditions of this permit-see review notes and plan annotations.
|
FIR08-00424
| INSP-Conference | 4/10/2009 | 4/10/2009 | 4/10/2009 3:50:21 PM | P | DONE |
|
|
Regarding items needed for permit final.
|
FIR08-00018
| INSP-Sprinkler Rough-in/Hydro | 4/9/2009 | 4/10/2009 | 4/10/2009 3:49:44 PM | A | PART |
|
|
Standpipe flow testing at the rooftop hose valves east and west sides completed satisfactory.
|
FIR09-00121
| INSP-Final Inspection | 4/9/2009 | 4/10/2009 | 4/10/2009 3:48:07 PM | A | FAIL |
|
|
The new manual pull station at the second floor failed to function. Notification devices tested okay.
|
BLD08-01848
| FIRE-Final Inspection | 4/9/2009 | 4/10/2009 | 4/10/2009 11:36:39 AM | A | PASS |
|
|
Correction items verified for completion, fire life safety finaled.
|