Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00108 INSP-Sprinkler Rough-in4/9/20134/10/20134/11/2013 7:08:59 AMPPART
Inspection for cover at the 3rd floor grid ceilings installed to date- Noted items include three missing hangers, overspacing at two areas, one room and portion of a corridor are incomplete, modification to coverage at the elevator lobby.
BLD13-00724 FIRE-Final Inspection4/9/20134/10/20134/11/2013 7:02:10 AMPDEFR
Insp. scheduled 4/11 PM
BLD13-00467 FIRE-Final Inspection4/10/20134/10/20134/10/2013 3:51:47 PMPPASS
Fire life safety inspection passed.
FIR13-00143 INSP-Final Inspection4/5/20134/10/20134/10/2013 3:35:54 PMAFAIL
Provide remote annunciator per review notes item #1, PIV is not electronically supervised, provide lock and label at the panel breaker. Per contractor, offsite monitoring could not be verified.
FIR12-00515 INSP-Final Inspection4/9/20134/10/20134/10/2013 8:57:41 AMACANC
Work will be complete by 11:30 am. Plans are in the riser room Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball