Inspections for the day of: Wednesday, April 10, 2013.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00855 Final4/9/20134/10/20134/10/2013 6:59:21 PMAFAIL
Alloway Elect Eric Nelson may still be on site if any questions. Phone # is ###-#### Phone #: ###-#### >> Inspection requested via web by brad williams NEC 250.52 Metal underground water pipe as part of the grounding electrode system shall be bonded within 5 ft.from point of entrance. With service upgrade NEC 250.140 Frames of ranges and clothes dryers shall be connected to the equipment grounding conductor
ELE13-00839 Final4/10/20134/10/20134/10/2013 2:41:18 PMPFAIL
>> Inspection requested via web by Mike A/C seal tight flex has break,exsposing conductors. Flex requires a strap
ELE13-00850 Electrical Rough-In4/9/20134/10/20134/10/2013 2:17:01 PMPPASS
pool bonding Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack rough-in ok
ELE13-00855 Permanent Service4/10/20134/10/20134/10/2013 1:43:03 PMPPASS
p/s o/h rec ok
ELE13-00830 Final4/9/20134/10/20134/10/2013 1:02:49 PMPFAIL
Someone is supposed to be there. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Panel directory not completed
ELE13-00455 Electrical Rough-In4/10/20134/10/20134/10/2013 12:05:48 PMPNR
Rough-in soffit. Wade on site. ###-#### Phone #: ###-#### >> Inspection requested via web by Bryan Atkins Not ready
ELE13-00263 Electrical Rough-In4/10/20134/10/20134/10/2013 11:37:52 AMPPASS
Last two pony walls in care areas Phone #: ###-#### >> Inspection requested via web by Patrick D Gill rough-in ok cover
ELE13-00175 Final4/9/20134/10/20134/10/2013 10:30:35 AMAPASS
Contact: Lyle Dean Phone #: ###-#### >> Inspection requested via web by Deb Gooden final ok nice job!
ELE12-01410 Electrical Rough-In4/9/20134/10/20134/10/2013 9:43:14 AMAPASS
Contact: Clay Freinwald - ceiling inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover ceiling grid 1500,1600,1700, and control room
ELE13-00715 Final4/9/20134/10/20134/10/2013 9:02:26 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Louis Keller final ok
ELE13-00086 Electrical Rough-In4/9/20134/10/20134/10/2013 8:40:56 AMAPASS
Dave. Underground. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy rough-in ok cover east half parking lot, conduits between 3 pole bases