Inspections for the day of: Friday, April 10, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-00927 Rough-In Permanent Service4/10/20154/10/20154/10/2015 3:27:01 PMPPASS
cody is the contact on site at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
ELE15-00974 Final4/9/20154/10/20154/10/2015 2:56:03 PMPPASS
Jess(contractor - ###-####)//Please call tenant for access(Ben -###-####) Phone #: ###-#### Final ok
ELE15-00940 Conference4/10/20154/10/20154/10/2015 2:42:07 PMPDONE
Phone #: 2532415028 >> Inspection requested via mobile web by Mike Discussed junctions must be accessible. kitchen layout for counter tops and islands, and type of receptacles required. Multi-wire branch circuits, handle ties.
ELE15-00765 Electrical Rough-In4/2/20154/10/20154/10/2015 1:47:39 PMPDONE
Check for illegal wiring progress back walkway and to carport. Property management working with contractor to repair wiring not up to code.
ELE14-03156 Final4/10/20154/10/20154/10/2015 1:47:30 PMPFAIL
Garage code 5550. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov 110.3 receptacle outlet not working in finished portion of basement hall.
210.8- GFCI protection shall be provided for all 120 volt receptacle outlets installed in unfinished portion of basement.
410.10(D)- Luminaire installed over edge of shower shall be rated for damp location.
410.16- All closet luminaires shall have totally enclosed lamps.
314.15- Light openings on outside of house shall have blank covers rated for damp locations.
334.80- #6 NM cable for hot tub ampacity shall not exceed 55 amps. Prewire shall have GFCI protection.
408.7- Hot tub panel unused openings shall be closed.
314.23- Out light boxes shall be securely mounted.
ELE15-00981 Final4/9/20154/10/20154/10/2015 11:40:44 AMAPASS
Work done for Bodell Construction. You need to check in with the security guard, cell tower equipment located behind Verizon Wireless switch building. Gate code 7208# Phone #: ###-#### Inspection requested via web by Rhonda Zamagni Final ok
ELE13-03105 Electrical Rough-In4/9/20154/10/20154/10/2015 11:08:34 AMAPASS
Entry and restroom ceiling cover Phone #: ###-#### Inspection requested via web by matt miller Did prelimary walk through building, disconnecting means for misc equipment above 6'7" will relocate. Grid rough in ok cover
ELE15-00573 Rough-In Permanent Service4/9/20154/10/20154/10/2015 11:08:16 AMAFAIL
Phone #: ###-#### Inspection requested via web by Heath Thomas 314.16(A)- 2 1/8"x4"x1 1/2" metal box has 10.3 cubic inch allowance 14 cubic inches wire and device installed.
334.30- UF shall be secured with in 12" of all boxes. Island
ELE15-00135 Final4/9/20154/10/20154/10/2015 9:17:09 AMAPASS
If you have any questions, please call the office. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
ELE15-00936 Temporary Service4/9/20154/10/20154/10/2015 8:38:18 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s u/g n ok
ELE15-00642 Final4/9/20154/10/20154/9/2015 2:42:57 PMAPASS
Lynn Phone #: ###-#### Final ok