Inspections for the day of: Tuesday, April 10, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01195 Electrical Rough-In4/10/20184/10/20184/10/2018 2:21:01 PMPFAIL
Wall cover please Phone #: ###-#### Inspection requested via web by Kyle Lott
300.4- MC run thru bored holes that do not maintain 1 1/4" from framing surface shall be protected from damage.
300.4- MC shall not be secured with in 1 1/4" from faming surface.
314.17- Unused knockouts shall be closed by approved means.
362.30- ENT shall be secured at intervals not to exceed 3' and shall be secured with in 3' of terminations.
590.6- All temp power used for construction shall have GFCI protection.
ELE18-01354 Final4/10/20184/10/20184/10/2018 1:39:28 PMPPASS
Phone #: ###-#### Inspection requested via web by steve ragan
Final ok
ELE18-01354 Electrical Rough-In4/10/20184/10/20184/10/2018 1:16:17 PMPPASS
Phone #: ###-#### Inspection requested via web by steve ragan
Conduits surface mounted, firewall penetration sealed. Rough in ok cover
ELE18-00286 Final4/10/20184/10/20184/10/2018 12:34:27 PMPPASS
Phone #: ###-#### Inspection requested via web by Lars Johnson Final ok
ELE17-03291 Rough-In Permanent Service4/9/20184/10/20184/10/2018 11:32:24 AMAPASS
call Dean with questions ###-#### Phone #: ###-#### Inspection requested via web by A.M.E. Office
22 k rated main overcurrent devices, contractor to calculate and post by final.
p/s u/g n ok
ELE18-01362 Rough-In Permanent Service4/9/20184/10/20184/10/2018 10:57:56 AMAPASS
Phone #: ###-#### Inspection requested via web by Paula Gratiot
Rough in ok cover p/s u/g n ok
ELE17-03293 Permanent Service4/9/20184/10/20184/10/2018 10:57:37 AMAPASS
call Dean with questions ###-#### Phone #: ###-#### Inspection requested via web by A.M.E. Office
22k rated main overcurrent devices, contractor to calculate and post by final.
p/s u/g n ok
ELE18-00343 Final4/10/20184/10/20184/10/2018 9:44:46 AMAPASS
please call 30 min prior to gain entrance Phone #: ###-#### Inspection requested via web by John Edwards
Final ok
ELE17-02895 Final4/9/20184/10/20184/10/2018 9:31:22 AMAFAIL
Garage code 1155E Phone #: ###-#### Inspection requested via web by Alan Lusk
110.14- Disimilar metals shall not come in contact. West AC splice copper and aluminum wire nutted together.
210.8- Receptacle outlets located with in 6' of a sink shall have GFCI protection. 120 volt dryer receptacle.