ELE18-01195
| Electrical Rough-In | 4/10/2018 | 4/10/2018 | 4/10/2018 2:21:01 PM | P | FAIL |
|
|
Wall cover please Phone #: ###-#### Inspection requested via web by Kyle Lott 300.4- MC run thru bored holes that do not maintain 1 1/4" from framing surface shall be protected from damage. 300.4- MC shall not be secured with in 1 1/4" from faming surface. 314.17- Unused knockouts shall be closed by approved means. 362.30- ENT shall be secured at intervals not to exceed 3' and shall be secured with in 3' of terminations. 590.6- All temp power used for construction shall have GFCI protection.
|
ELE18-01354
| Final | 4/10/2018 | 4/10/2018 | 4/10/2018 1:39:28 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Final ok
|
ELE18-01354
| Electrical Rough-In | 4/10/2018 | 4/10/2018 | 4/10/2018 1:16:17 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Conduits surface mounted, firewall penetration sealed. Rough in ok cover
|
ELE18-00286
| Final | 4/10/2018 | 4/10/2018 | 4/10/2018 12:34:27 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Lars Johnson Final ok
|
ELE17-03291
| Rough-In Permanent Service | 4/9/2018 | 4/10/2018 | 4/10/2018 11:32:24 AM | A | PASS |
|
|
call Dean with questions ###-#### Phone #: ###-#### Inspection requested via web by A.M.E. Office 22 k rated main overcurrent devices, contractor to calculate and post by final. p/s u/g n ok
|
ELE18-01362
| Rough-In Permanent Service | 4/9/2018 | 4/10/2018 | 4/10/2018 10:57:56 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Paula Gratiot Rough in ok cover p/s u/g n ok
|
ELE17-03293
| Permanent Service | 4/9/2018 | 4/10/2018 | 4/10/2018 10:57:37 AM | A | PASS |
|
|
call Dean with questions ###-#### Phone #: ###-#### Inspection requested via web by A.M.E. Office 22k rated main overcurrent devices, contractor to calculate and post by final. p/s u/g n ok
|
ELE18-00343
| Final | 4/10/2018 | 4/10/2018 | 4/10/2018 9:44:46 AM | A | PASS |
|
|
please call 30 min prior to gain entrance Phone #: ###-#### Inspection requested via web by John Edwards Final ok
|
ELE17-02895
| Final | 4/9/2018 | 4/10/2018 | 4/10/2018 9:31:22 AM | A | FAIL |
|
|
Garage code 1155E Phone #: ###-#### Inspection requested via web by Alan Lusk 110.14- Disimilar metals shall not come in contact. West AC splice copper and aluminum wire nutted together. 210.8- Receptacle outlets located with in 6' of a sink shall have GFCI protection. 120 volt dryer receptacle.
|