Inspections for the day of: Tuesday, April 10, 2018.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00171 INSP-Sprinkler Rough-in4/10/20184/10/20184/10/2018 2:48:34 PMPPASS
Rough in inspection for area of work complete.
FIR18-00173 INSP-Sprinkler Rough-in4/10/20184/10/20184/10/2018 2:46:47 PMPPASS
Rough in inspection for area of work complete.
FIR18-00253 INSP-Sprinkler Rough-in4/10/20184/10/20184/10/2018 2:45:04 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
FIR18-00253 INSP-Sprinkler Rough-in/Hydro4/9/20184/10/20184/10/2018 2:43:34 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.
FIR18-00171 INSP-Sprinkler Rough-in/Hydro4/9/20184/10/20184/10/2018 2:43:16 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.
FIR18-00173 INSP-Sprinkler Rough-in/Hydro4/9/20184/10/20184/10/2018 2:42:54 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.
FIR18-00252 INSP-Final Inspection4/9/20184/10/20184/10/2018 2:41:48 PMPPASS
Final fire alarm inspection for area of work complete.
FIR18-00182 INSP-Sprinkler Rough-in4/10/20184/10/20184/10/2018 9:37:19 AMPPASS
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover.
NAF18-00050 INSP-Sprinkler Rough-in4/9/20184/10/20184/10/2018 8:27:44 AMAPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR18-00108 INSP-Final Inspection4/9/20184/10/20184/10/2018 6:56:29 AMACANC
Please call 1/2 before arriving. Thanks Phone #: ###-#### >> Inspection requested via web by david davis Inspection cancelled from web by: david davis