Inspections for the day of: Thursday, April 11, 2002.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD00-02292 FIRE-Final Inspection4/10/20024/11/20024/11/2002 12:00:00 AMAPASS
Fire life/safety, fire alarm and fire sprinkler finaled 4/10/2002 3:33:58 PM
FIR02-00090 INSP-Sprinkler Rough-in4/11/20024/11/20024/11/2002 12:00:00 AMPPART
restrooms, corridor, electrical room and small room next to it OK for cover 4/12/2002 9:16:07 AM
FIR02-00057 INSP-Sprinkler Rough-in/Hydro4/11/20024/11/20024/11/2002 12:00:00 AMPFAIL
pendant heads are over space on eastside north/south running wall. Pendant head needs to be added at soffit point and upright heads need to be added at soffit point above ceiling. Exact locations have been marked on approved plans. I told contractor its OK to cover other areas 4/11/2002 5:21:41 PM