ELE05-01050
| Electrical Rough-In | 4/8/2005 | 4/11/2005 | 4/11/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 4/8/2005 at 11:53:56 AM. Contact: ###-####. ok to cover u/g for pipng around pool 4/11/2005 8:34:20 AM
|
ELE05-01182
| Final | 4/8/2005 | 4/11/2005 | 4/11/2005 12:00:00 AM | A | PASS |
|
|
Spa Final please; Phone #: ###-#### ok to final 4/11/2005 9:57:13 AM
|
ELE05-01139
| Rough-In Permanent Service | 4/8/2005 | 4/11/2005 | 4/11/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 4/8/2005 at 2:52:26 PM. Contact: ###-####. ok to cover for conc encased electrode 4/11/2005 10:09:03 AM
|
ELE05-01197
| Rough-In Permanent Service | 4/8/2005 | 4/11/2005 | 4/11/2005 12:00:00 AM | A | PASS |
|
|
dino ###-#### called contr, left survey for add 2 recpts per 210.52 (A) (2). one by entry door and one in mbr. ric ok, p/s u/g n ok 4/11/2005 9:11:07 AM
|
ELE05-00696
| Final | 4/8/2005 | 4/11/2005 | 4/11/2005 12:00:00 AM | A | FAIL |
|
|
Thank you ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, left corr notice, 210.8 recpts in kitchen shall be gfci protected, 210.52(C)(1) recpts shall be placed so no point is over 24" along wall line, 352.30(A) rnc shall be supported within 3' of box BCC no code violations shall be retained. 4/11/2005 8:21:10 AM
|
ELE05-00717
| Rough-In Permanent Service | 4/10/2005 | 4/11/2005 | 4/11/2005 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 4/10/2005 at 10:04:34 PM. Contact: ###-####. met with owner, outside ready, but he needs to provide ground lug inside at sub-panel 4/11/2005 3:48:29 PM
|
ELE04-03672
| Rough-In Permanent Service | 4/11/2005 | 4/11/2005 | 4/11/2005 12:00:00 AM | P | CANC |
|
|
re-inspection on service; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen called wrong address for insp 4/11/2005 4:39:48 PM
|
ELE05-01180
| Electrical Rough-In | 4/11/2005 | 4/11/2005 | 4/11/2005 12:00:00 AM | P | PASS |
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corrections made, ric ok 4/11/2005 12:16:05 PM
|
ELE05-01098
| Electrical Rough-In | 4/11/2005 | 4/11/2005 | 4/11/2005 12:00:00 AM | P | FAIL |
|
|
david; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left corr notice, 300.4(D) 1 1/4" shall be maintained from edge if framing members,250.148(B) ground connections in box shall be continuous, 210.52(B)(2) hood shall not be on small appliance ckt, 110.12(A) un-used openings shall be closed in range box, 210.52(A)(1) &(2) 6' receptacle spacing shall be maintained, 310.15(B)(6) feeders too small for 200A panel 4/11/2005 1:35:29 PM
|
ELE05-01040
| Electrical Rough-In | 4/11/2005 | 4/11/2005 | 4/11/2005 12:00:00 AM | P | PASS |
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Barbara Moore walls downstairs only ok to cover. Called contr. Rest to be surface run. 4/11/2005 2:22:24 PM
|
ELE05-00717
| Rough-In Permanent Service | 4/10/2005 | 4/11/2005 | 4/10/2005 10:01:29 PM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 4/10/2005 at 9:58:48 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Apr 10 2005 10:01PM.
|