FIR04-00358
| INSP-Sprinkler Rough-in | 4/11/2005 | 4/11/2005 | 4/11/2005 4:31:15 PM | P | PART |
|
|
See plans with todays date for areas ok to cover. Resubmittals are required for changes in piping, lobby and room above ceiling
|
FIR05-00206
| INSP-Sprinkler Rough-in | 4/11/2005 | 4/11/2005 | 4/11/2005 4:30:17 PM | P | PART |
|
|
Underground supply piping stub out ok to cover
|
BLD04-01752
| FIRE-Final Inspection | 4/8/2005 | 4/11/2005 | 4/11/2005 3:08:05 PM | A | FAIL |
|
|
Duct smoke detectors are not wired for immediate shutdown of the hvac units. Need to rewire and retest.
|
BLD05-00007
| FIRE-Final Inspection | 4/11/2005 | 4/11/2005 | 4/11/2005 1:57:59 PM | P | CANC |
|
|
Cancel, contractor needs fire alarm permit finaled.
|
FIR05-00195
| INSP-Sprinkler Rough-in/Hydro | 4/11/2005 | 4/11/2005 | 4/11/2005 1:55:35 PM | P | PASS |
|
|
Sprinkler piping is ok to cover
|
BLD05-00107
| FIRE-Final Inspection | 4/8/2005 | 4/11/2005 | 4/11/2005 1:23:08 PM | P | PART |
|
|
Heather ###-#### Finish tenting in the master bedroom and in the first floor office. Master bedroom has sprinkler pendant installed too close to the fire place. There is exposed 1" CPVC pipe on top of the arch entry ot the master bedroom. Must meet requi
|
FIR05-00045
| INSP-Sprinkler Rough-in | 4/11/2005 | 4/11/2005 | 4/11/2005 11:32:20 AM | P | FAIL |
|
|
Could not find plans to do the inspection
|
BLD04-02863
| FIRE-Final Inspection | 4/8/2005 | 4/11/2005 | 4/11/2005 10:18:58 AM | A | FAIL |
|
|
Still need approved hardware on the rear exit door and current inspection tags on the fire extinguishers
|
MIS05-00037
| FIR-Final | 4/8/2005 | 4/11/2005 | 4/11/2005 10:07:08 AM | A | PASS |
|
|
Fire life safety finaled.
|
BLD04-02942
| FIRE-Final Inspection | 4/8/2005 | 4/11/2005 | 4/11/2005 9:59:33 AM | A | FAIL |
|
|
Fail, install and test emergency lights as marked on plans, verify door hardware.
|
MIS05-00035
| FIR-Final | 4/8/2005 | 4/11/2005 | 4/11/2005 9:56:44 AM | A | FAIL |
|
|
tony ###-#### Fail inspecction, no access to facility.
|
BLD05-00337
| FIRE-Final Inspection | 4/8/2005 | 4/11/2005 | 4/11/2005 9:22:42 AM | A | FAIL |
|
|
Fail, repair or remove exit signs over west and east doors, remove manual flush bolts from main entry exit, provide approved door hardware on SE door and main double exit doors, provide annual inspection for fire extinguishers, remove latch and bar from
|
MIS05-00036
| FIR-Final | 4/8/2005 | 4/11/2005 | 4/11/2005 8:46:39 AM | A | FAIL |
|
|
Still need to repair the existing emergency light
|
MIS05-00038
| FIR-Final | 4/8/2005 | 4/11/2005 | 4/11/2005 8:42:47 AM | A | PASS |
|
|
Fire life safety finaled
|
BLD04-02864
| FIRE-Final Inspection | 4/8/2005 | 4/11/2005 | 4/11/2005 8:36:49 AM | A | FAIL |
|
|
No approved drawings on site. Pointed out some problems like nonfunctional exit signs, thumbturns and no tags on fire extinguishers to the manager on site.
|
BLD04-01048
| FIRE-Final Inspection | 4/8/2005 | 4/11/2005 | 4/11/2005 8:17:21 AM | A | CANC |
|
|
robie -###-####
|