Inspections for the day of: Monday, April 11, 2005.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00358 INSP-Sprinkler Rough-in4/11/20054/11/20054/11/2005 4:31:15 PMPPART
See plans with todays date for areas ok to cover. Resubmittals are required for changes in piping, lobby and room above ceiling
FIR05-00206 INSP-Sprinkler Rough-in4/11/20054/11/20054/11/2005 4:30:17 PMPPART
Underground supply piping stub out ok to cover
BLD04-01752 FIRE-Final Inspection4/8/20054/11/20054/11/2005 3:08:05 PMAFAIL
Duct smoke detectors are not wired for immediate shutdown of the hvac units. Need to rewire and retest.
BLD05-00007 FIRE-Final Inspection4/11/20054/11/20054/11/2005 1:57:59 PMPCANC
Cancel, contractor needs fire alarm permit finaled.
FIR05-00195 INSP-Sprinkler Rough-in/Hydro4/11/20054/11/20054/11/2005 1:55:35 PMPPASS
Sprinkler piping is ok to cover
BLD05-00107 FIRE-Final Inspection4/8/20054/11/20054/11/2005 1:23:08 PMPPART
Heather ###-#### Finish tenting in the master bedroom and in the first floor office. Master bedroom has sprinkler pendant installed too close to the fire place. There is exposed 1" CPVC pipe on top of the arch entry ot the master bedroom. Must meet requi
FIR05-00045 INSP-Sprinkler Rough-in4/11/20054/11/20054/11/2005 11:32:20 AMPFAIL
Could not find plans to do the inspection
BLD04-02863 FIRE-Final Inspection4/8/20054/11/20054/11/2005 10:18:58 AMAFAIL
Still need approved hardware on the rear exit door and current inspection tags on the fire extinguishers
MIS05-00037 FIR-Final4/8/20054/11/20054/11/2005 10:07:08 AMAPASS
Fire life safety finaled.
BLD04-02942 FIRE-Final Inspection4/8/20054/11/20054/11/2005 9:59:33 AMAFAIL
Fail, install and test emergency lights as marked on plans, verify door hardware.
MIS05-00035 FIR-Final4/8/20054/11/20054/11/2005 9:56:44 AMAFAIL
tony ###-#### Fail inspecction, no access to facility.
BLD05-00337 FIRE-Final Inspection4/8/20054/11/20054/11/2005 9:22:42 AMAFAIL
Fail, repair or remove exit signs over west and east doors, remove manual flush bolts from main entry exit, provide approved door hardware on SE door and main double exit doors, provide annual inspection for fire extinguishers, remove latch and bar from
MIS05-00036 FIR-Final4/8/20054/11/20054/11/2005 8:46:39 AMAFAIL
Still need to repair the existing emergency light
MIS05-00038 FIR-Final4/8/20054/11/20054/11/2005 8:42:47 AMAPASS
Fire life safety finaled
BLD04-02864 FIRE-Final Inspection4/8/20054/11/20054/11/2005 8:36:49 AMAFAIL
No approved drawings on site. Pointed out some problems like nonfunctional exit signs, thumbturns and no tags on fire extinguishers to the manager on site.
BLD04-01048 FIRE-Final Inspection4/8/20054/11/20054/11/2005 8:17:21 AMACANC
robie -###-####