FIR05-00278
| FIR-Aging Inspection | 4/11/2006 | 4/11/2006 | 4/17/2006 3:23:26 PM | | DONE |
|
|
Scheduled for final.
|
BLD04-00949
| FIRE-Final Inspection | 4/11/2006 | 4/11/2006 | 4/11/2006 5:46:13 PM | P | FAIL |
|
|
Fire alarm and fire sprinkler permits associated with this project must be inspected and approved previous to a life safety final inspection.
|
FIR05-00667
| INSP-Sprinkler Rough-in/Hydro | 4/11/2006 | 4/11/2006 | 4/11/2006 5:42:52 PM | P | DEFR |
|
|
Scheduled by a contractor via Hello! on 4/11/2006 at 8:37:28 AM. Contact: ###-####.
|
FIR06-00156
| INSP-Final Inspection | 4/11/2006 | 4/11/2006 | 4/11/2006 5:42:38 PM | P | DEFR |
|
|
Scheduled by a contractor via Hello! on 4/11/2006 at 8:35:37 AM. Contact: ###-####.
|
FIR05-00174
| INSP-Final Inspection | 4/11/2006 | 4/11/2006 | 4/11/2006 5:36:25 PM | P | PASS |
|
|
UG permit finaled.
|
FIR05-00405
| INSP-Final Inspection | 4/11/2006 | 4/11/2006 | 4/11/2006 5:33:50 PM | P | PASS |
|
|
Required corrections are complete, permit finaled.
|
FIR05-00272
| INSP-Sprinkler Rough-in | 4/10/2006 | 4/11/2006 | 4/11/2006 5:30:05 PM | P | CANC |
|
|
No time available for this inspection today, to be rescheduled per agreement with contractor.
|
FIR06-00248
| INSP-Final Inspection | 4/11/2006 | 4/11/2006 | 4/11/2006 5:28:38 PM | P | PASS |
|
|
Fire alarm tested satisfactory, inspection passed.
|
FIR06-00149
| INSP-Sprinkler Rough-in | 4/10/2006 | 4/11/2006 | 4/11/2006 4:01:58 PM | P | PART |
|
|
Overhead rough-in is good for cover, field modifications such as added heads at some locations due to obstructions which do not show on the approved plan must be reflected on as-built drawings, be aware of possible light fixture obstructions at some areas, UG supply line flush performed satisfactory.
|
FIR06-00053
| INSP-Supply line flush | 4/7/2006 | 4/11/2006 | 4/11/2006 3:17:01 PM | P | DEFR |
|
|
No time available to complete this inspection today, to be rescheduled per conversation with contractor.
|
FIR05-00449
| INSP-Alarm Testing | 4/10/2006 | 4/11/2006 | 4/11/2006 3:15:43 PM | A | FAIL |
|
|
Detection and notification devices tested on the 5th and 6th floors today, voice evac failed to function properly, ID, SD and manual pulls tested okay, need to date batteries in the 6th floor nac panel, elevator lobby smokes not tested at this time.
|
FIR05-00804
| INSP-Final Inspection | 4/10/2006 | 4/11/2006 | 4/11/2006 11:50:20 AM | A | PASS |
|
|
Fire alarm functioned properly, inspection passed.
|
FIR05-00712
| INSP-Final Inspection | 4/10/2006 | 4/11/2006 | 4/11/2006 11:34:39 AM | P | CANC |
|
|
Forrest, We like to schedule for 1:30 again to finish this off. Any questions call us.; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
FIR05-00405
| INSP-Final Inspection | 4/10/2006 | 4/11/2006 | 4/11/2006 10:30:49 AM | A | NR |
|
|
Permit not ready for final pending project related alarm work.
|
BLD05-02631
| FIRE-Final Inspection | 4/10/2006 | 4/11/2006 | 4/11/2006 10:24:41 AM | A | PASS |
|
|
Life safety inspection satisfactory for vanilla finish, contractor to install visual lock indicator at the main entry/exit today as discussed.
|
BLD05-03067
| FIRE-Final Inspection | 4/10/2006 | 4/11/2006 | 4/11/2006 10:22:31 AM | A | PASS |
|
|
Items on previous inspection correction notice have been completed as required, project related alarm and sprinkler permits are finaled, life safety passed.
|