Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-02618 FIRE-Conference4/3/20064/10/2006 P 
Follow-up on correction notice. One week was given to start work ending on 4/10/06.
BLD02-02216 FIRE-Conference4/3/20064/10/2006 P 
Follow-up on correction notice. One week was given to start work ending on 4/10/06.
BLD04-00469 BLD-Aging Inspection4/11/20064/11/20064/12/2006 11:54:11 AM NR
I spoke to clint and he would find the drawings and call in the inspection for tommorrow
FIR06-00146 INSP-Sprinkler Rough-in/Hydro4/11/20064/11/20064/11/2006 3:33:28 PMPPASS
Need to provide additional upright sprinklers as discussed in the dormer pockets and the pocket found below the decking near the main entrance. Piping is ok to cover. These items can be verified at final.
FIR06-00075 INSP-Sprinkler Rough-in4/11/20064/11/20064/11/2006 3:31:09 PMPFAIL
Provide EQ bracing and access for verification in the exterior canopy at the point of connection, provide access for north branchline in main lobby, provide retainer strap on 1" piping in southeast corner of the main lobbly, provide access for piping verification in front exterior canopy and the new 2" main needs connected to the existing 3" main. Needs hydro tested and other final stuff done.
BLD06-00004 FIRE-Final Inspection4/11/20064/11/20064/11/2006 2:30:02 PMPFAIL
Provide approved door hardware on the exterior door and the common door per sheet 3 of the approved building plans.
FIR05-00479 FIR-Aging Inspection4/11/20064/11/20064/11/2006 12:06:22 PM NR
Work is in progress
FIR06-00065 INSP-Sprinkler Rough-in4/10/20064/11/20064/11/2006 12:04:45 PMAPART
Canopy is ok to cover but one upright sprinkler head is overspaced from the west end of the central big canopy. See marked plans for exact location.
BLD06-00659 FIRE-Final Inspection4/10/20064/11/20064/11/2006 11:36:15 AMAPASS
Life safety finaled
FIR06-00214 INSP-Final Inspection4/10/20064/11/20064/11/2006 10:41:47 AMAPASS
Permit finaled