Inspections for the day of: Wednesday, April 11, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00108 ELE-Aging Inspection4/11/20074/11/20074/11/2007 2:42:02 PM DONE
wsuc
ELE07-00121 ELE-Aging Inspection4/11/20074/11/20074/11/2007 2:41:30 PM DONE
WSUC
ELE07-01218 Final4/11/20074/11/20074/11/2007 2:40:14 PMPPASS
Chuck; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
ok
ELE07-01218 Permanent Service4/11/20074/11/20074/11/2007 2:39:59 PMPPASS
Chuck; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
p/s u/g new ok
ELE07-01210 Temporary Service4/11/20074/11/20074/11/2007 1:59:51 PMPPASS
temp pole, behind existing house Phone #: ###-#### t/s o/h new ok
ELE07-00761 Rough-In Permanent Service4/11/20074/11/20074/11/2007 1:34:24 PMPPASS
On-site contact: Gene ###-#### Phone #: ###-#### r/i all 4 units ok p/s u/g new ok
ELE07-01226 Conference4/10/20074/11/20074/11/2007 10:33:48 AMADONE
Rocky pls call 30 min prior. ready at 8:00 am.; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ok
ELE07-01209 Temporary Service4/10/20074/11/20074/11/2007 10:10:54 AMAFAIL
Temp pole is near the xfmer at the south end of the building 100'' east of Sage Construction job trailer. Phone #: ###-#### x0000 corr. called 110.3(B) install manufactures tie bar between neutral buses, use manufactures breakers only, 110.14(A) tighten all screws at bond bushing, 110.12(C) clean all dirt from T/S, 250.64(B) protect #8 GEC, 312.5 use conn. for GEC
ELE06-03280 Permanent Service4/10/20074/11/20074/11/2007 9:17:01 AMAPASS
Please inspect main service to bldg (see MDP Room). Thankyou. Phone #: ###-#### p/s u/g new ok tag on CT meter
ELE06-03280 Electrical Rough-In4/11/20074/11/20074/11/2007 9:16:02 AMAPART
Please inspect main service to bldg (see MDP Room). Thankyou. Phone #: ###-#### soffits ok
ELE07-01019 Permanent Service4/6/20074/11/20074/11/2007 8:11:05 AMAFAIL
100amp service upgrade, any questions call George @ ###-#### Phone #: ###-####
230.9 called needs required clearence over roof
ELE07-01020 Permanent Service4/10/20074/11/20074/11/2007 7:40:53 AMAPASS
final on new service for garage. Any questions call Jimmy @ ###-#### Phone #: ###-#### p/s o/h new ok