Inspections for the day of: Friday, April 11, 2008.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-00551 FIRE-Final Inspection4/10/20084/11/20084/11/2008 2:46:09 PMAFAIL
Tenant address as posted is not correct per city addressing department, exit door to the west must remain clear of obstructions.
BLD07-01372 FIRE-Final Inspection4/10/20084/11/20084/11/2008 2:36:32 PMAFAIL
Repair exit sign at the SE classroom, provide lever hardware at the second marked exit door from the art room, noted exit doors are blocked or covered by curtains at five areas-see approved plans for locations-exit doors are to be maintained free from obstructions at all times per IFC and IBC requirements.
FIR06-00540 INSP-Final Inspection4/10/20084/11/20084/11/2008 12:48:11 PMAFAIL
See 12 item correction notice left on site for a list of defficient items including descriptors at several tamper and flow switches, missing head boxes and spare stock of sprinklers, noted missing coverage at four new stairwell pressure fan rooms at the mech. penthouse, need to demo class 2 fire hose cabinet valves no longer connected at the penthouse, roof and basement levels, missing sprinkler protection at the penthouse level cooling tower room enclosure, repair 2nd floor NE flow switch and NE basement tamper, supervisory signals shall report at the panel within 90 seconds per NFPA 72, provide signage at stairway standpipe isolation control valves, repair tamper and flow switches at the 5th floor NE riser, need signage at the doors to control valve rooms on the 5th floor NE and SW risers, noted seismic ugrades for the standpipe floor level penetrations have not been provided.