FIR08-00802
| FIR-Aging Inspection | 4/11/2011 | 4/11/2011 | 4/18/2011 4:32:07 PM | | DONE |
|
|
Modified permit scope finaled due to building demo work.
|
FIR10-00637
| INSP-Final Inspection | 4/11/2011 | 4/11/2011 | 4/12/2011 5:07:18 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR10-00637
| INSP-Supply line flush | 4/11/2011 | 4/11/2011 | 4/11/2011 3:43:41 PM | P | DONE |
|
|
UG supply line flush completed okay.
|
BLD09-01986
| FIRE-Final Inspection | 4/11/2011 | 4/11/2011 | 4/11/2011 3:41:26 PM | P | FAIL |
|
|
Post max occupant load sign at the great room, repair one exit sign at the west side, remove keyed deadbolt locks at three interior doors. See plan review comments for details.
|
BLD11-00215
| FIRE-Final Inspection | 4/11/2011 | 4/11/2011 | 4/11/2011 2:37:00 PM | P | PASS |
|
|
Life safety inspection passed. NOTE: Signature card not available on site.
|
BLD11-00357
| FIRE-Final Inspection | 4/8/2011 | 4/11/2011 | 4/11/2011 2:34:38 PM | A | PASS |
|
|
Noted corrections finished. Fire life safety finaled.
|
BLD11-00505
| FIRE-Final Inspection | 4/8/2011 | 4/11/2011 | 4/11/2011 11:55:29 AM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD10-02614
| FIRE-Final Inspection | 4/8/2011 | 4/11/2011 | 4/11/2011 11:26:47 AM | A | FAIL |
|
|
Basement fire sprinkler system control valve at the DCVA #2 shutoff is closed. Noted two EM lights at the basement level are not functional. NOTE: Fire extinguisher certifications are now current.
|