FIR12-00118
| INSP-Final Inspection | 4/11/2012 | 4/11/2012 | 4/11/2012 3:58:55 PM | P | CANC |
|
|
Canceled due to the fire alarm tech being on a service call and my schedule. Being rescheduled for tomorrow morning.
|
FIR12-00118
| INSP-Sprinkler Rough-in/Hydro | 4/11/2012 | 4/11/2012 | 4/11/2012 3:42:24 PM | P | CANC |
|
|
A Fire Final needed to be set up instead of the sprinkler rough-in/hydro inspection.
|
FIR12-00161
| INSP-Sprinkler Rough-in | 4/10/2012 | 4/11/2012 | 4/11/2012 3:25:13 PM | P | PASS |
|
|
See the city approved plans for locations on the first, second and fourth floor where the sprinkler piping can be covered.
|
FIR12-00180
| INSP-Final Inspection | 4/11/2012 | 4/11/2012 | 4/11/2012 3:00:27 PM | P | PASS |
|
|
Permit finaled.
|
BLD12-00658
| FIRE-Final Inspection | 4/10/2012 | 4/11/2012 | 4/11/2012 11:28:56 AM | A | FAIL |
|
|
Remove the deadbolt from the rear exit door. Remove the two old fire extinguishers and provide an annual inspection for the remaining fire extinguisher.
|
FIR09-00263
| FIR-Aging Inspection | 4/11/2012 | 4/11/2012 | 4/11/2012 10:47:15 AM | | PASS |
|
|
I spoke to Matt about getting this permit voided.
|
BLD12-00663
| FIRE-Final Inspection | 4/10/2012 | 4/11/2012 | 4/11/2012 9:40:48 AM | A | FAIL |
|
|
Remove the round knob at the main exit, lever hardware is ok. Remove the thumbturn on the main exit dead bolt, keyed is ok. Provide "Door to Remain Unlocked When Building is Occupied" sticker at the main exit. Provide address numbers of a contrasting color and atleast 4" in height facing the street.
|