Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00141 INSP-Final Inspection4/11/20134/11/20134/11/2013 3:58:54 PMPFAIL
Items tested include the phone lines, sprinkler tamper switches and elevator recall. Items needed to be approved through plan review is that the firemans hat can flash when a lobby smoke detector is activated (per code it is not allowed). Also when the wharehouse smoke detector is activated the doors open to the retail side not recall to the second floor. The duct detectors do shut down the hvac units but per Robert are wired wrong. He is going to correct this item and retest. There is one additional tamper switch not shown on the plans and the possiblility of deleting a module at the elevator. These changes will need to be shown on as-builts. I notified the building owner that the annual inspections of the sprinkler systems was overdue. He made a phone call to get the work scheduled.
FIR13-00020 INSP-Sprinkler Rough-in4/11/20134/11/20134/11/2013 3:49:58 PMPCANC
Overbooked . Lonnie is going to reschedule.
FIR13-00043 INSP-Final Inspection4/11/20134/11/20134/11/2013 3:37:32 PMPFAIL
As-builts were not on site for review.
FIR13-00030 INSP-Sprinkler Rough-in4/11/20134/11/20134/11/2013 3:34:52 PMPCANC
Overbooked. Troy is going to reschedule
FIR12-00574 INSP-Final Inspection4/11/20134/11/20134/11/2013 1:24:06 PMPFAIL
Forward flush passed inspection but can not final until the latest plans have been provided.
FIR12-00330 INSP-Final Inspection4/11/20134/11/20134/11/2013 1:19:15 PMPPASS
Permit finaled
FIR13-00156 INSP-Final Inspection4/11/20134/11/20134/11/2013 1:18:20 PMPPASS
permit finaled
FIR13-00156 INSP-Sprinkler Rough-in4/10/20134/11/20134/11/2013 1:17:37 PMAPASS
Sprinkler piping can be covered.
BLD13-00520 FIRE-Final Inspection4/11/20134/11/20134/11/2013 12:44:50 PMPPASS
Life safety passed
FIR13-00149 INSP-Final Inspection4/11/20134/11/20134/11/2013 12:43:56 PMPPASS
Permit finaled
FIR13-00043 INSP-Final Inspection4/10/20134/11/20134/11/2013 10:35:37 AMAFAIL
Valve for the forward flush broke and the plan modifications were not on site for review.
FIR12-00330 INSP-Final Inspection4/10/20134/11/20134/11/2013 10:33:30 AMAPASS
permit finaled
FIR13-00111 INSP-Final Inspection4/9/20134/11/20134/11/2013 8:51:22 AMAPASS
Permit finaled. The delay between the temporal codes seemed longer than usual but per the technician, Brian, it has ben timed and meets code.