FIR13-00668
| INSP-Final Inspection | 4/11/2014 | 4/11/2014 | 4/14/2014 2:46:33 PM | P | PASS |
|
|
Permit finaled
|
FIR14-00101
| INSP-Sprinkler Rough-in | 4/8/2014 | 4/11/2014 | 4/11/2014 3:21:25 PM | P | PASS |
|
|
Sprinkler piping is ok to cover. Rough-in passed
|
FIR14-00158
| INSP-Final Inspection | 4/10/2014 | 4/11/2014 | 4/11/2014 3:14:09 PM | P | PASS |
|
|
Permit finaled
|
FIR14-00203
| INSP-Final Inspection | 4/11/2014 | 4/11/2014 | 4/11/2014 2:47:52 PM | P | PASS |
|
|
Permit finaled
|
FIR12-00717
| INSP-Sprinkler Rough-in | 4/10/2014 | 4/11/2014 | 4/11/2014 2:47:29 PM | A | PASS |
|
|
See the city approved plans for locations marked "ok" where piping is ok to cover.
|
BLD14-00490
| FIRE-Final Inspection | 4/11/2014 | 4/11/2014 | 4/11/2014 1:02:39 PM | P | PASS |
|
|
Life safety passed. It appears the115cd fire alarm strobe on the north wall will provide coverage for this new area.
|
FIR14-00200
| INSP-Final Inspection | 4/11/2014 | 4/11/2014 | 4/11/2014 1:00:58 PM | P | PASS |
|
|
Permit finaled
|
FIR14-00200
| INSP-Sprinkler Rough-in | 4/11/2014 | 4/11/2014 | 4/11/2014 12:17:26 PM | P | PASS |
|
|
Rough-in passed
|
FIR14-00189
| INSP-Final Inspection | 4/10/2014 | 4/11/2014 | 4/11/2014 10:20:31 AM | A | PASS |
|
|
Permit finaled
|
FIR14-00203
| INSP-Sprinkler Rough-in/Hydro | 4/11/2014 | 4/11/2014 | 4/11/2014 10:20:07 AM | A | PASS |
|
|
|
FIR14-00133
| INSP-Final Inspection | 4/7/2014 | 4/11/2014 | 4/11/2014 10:16:46 AM | A | FAIL |
|
|
Permit can be finaled when the correct address has been provided and updated to the permit case.
|