Inspections for the day of: Monday, April 11, 2016.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00770 INSP-Sprinkler Rough-in4/11/20164/11/20164/11/2016 2:27:36 PMPFAIL
Plan Modifications Are Required. Could not perform/finish rough-in since not all of the r/c's (pendant heads) had been installed. I found a missing head in the second floor remote area. There are extensive pipe changes which includes routing and many additional fittings including changing from the approved sidewall heads to pendant heads in the garage areas. Patio sidewall heads have been re-routed. Hangers are missing and heads are overspaced. Some heads can't provide coverage due to shadowing caused by walls (instead of installing two heads as per the plans, the fitter is trying to use one head to provide coverage). No tenting has been installed yet. The Fire Dept Connection was in the process of being installed in another location that was not shown on the approved plans.
FIR15-00770 INSP-Sprinkler Rough-in/Hydro4/11/20164/11/20164/11/2016 2:14:46 PMPFAIL
Could not perform hydro since not all of the r/c's (pendant heads) had been installed. I found a missing head in the second floor remote area. There are extensive pipe changes which includes routing and many additional fittings including changing from the approved sidewall heads to pendant heads in the garage areas.
FIR16-00002 INSP-Final Inspection4/8/20164/11/20164/11/2016 12:02:51 PMAFAIL
The two standard responce pendants have not been changed to quick responce. Ron is going to walk the project and make sure all is right.
FIR16-00157 INSP-Final Inspection4/4/20164/11/20164/11/2016 9:21:11 AMAPASS
permit finaled