FIR17-00080
| INSP-Sprinkler Rough-in | 4/11/2017 | 4/11/2017 | 4/11/2017 2:44:25 PM | P | PART |
|
|
Resubmitted plans have been approved for the area inspected yesterday but insulation has been installed that blocks the CC2 heads on two branchlines.
|
BLD17-00708
| FIRE-Final Inspection | 4/5/2017 | 4/11/2017 | 4/11/2017 1:44:24 PM | P | CANC |
|
|
Scott Phone #: ###-####
|
BLD16-03962
| FIRE-Final Inspection | 4/11/2017 | 4/11/2017 | 4/11/2017 1:43:54 PM | P | FAIL |
|
|
Provide annual inspection for the fire extinguishers, provide verification of annual inspections for the building fire sprinkler and fire alarm systems, provide exit signs as per the city approved plans and remove the locking hardware from the warehouse to office area. Or call plan review and get exiting updated to utilize the warehouse door not shown on the plans. Also provide testing of the existing exit signs and emergency lights. Provide sticker at the main exit
|
FIR17-00080
| INSP-Sprinkler Rough-in | 4/11/2017 | 4/11/2017 | 4/11/2017 11:43:52 AM | P | PART |
|
|
This inspection was actually performed on 4/10/17 but was input under the wrong permit number.
Rough to cover inspection passed for area marked on the city approved plans. I noted one missing sprig up that was being installed as I waited. East canopy has not been built or piping installed yet. Plans need to be resubmitted for approval showing the changing of the standard heads to the CC2's prior to more cover inspections being approved.
|
BLD17-00708
| FIRE-Final Inspection | 4/5/2017 | 4/11/2017 | 4/11/2017 10:35:45 AM | A | FAIL |
|
|
Provide annual inspection for fire extinguisher, contact plan review for revised floor plan
|
FIR16-00665
| INSP-Sprinkler Rough-in/Hydro | 4/10/2017 | 4/11/2017 | 4/11/2017 10:33:49 AM | A | PASS |
|
|
Underground hydro test passed
|
FIR16-00738
| INSP-Sprinkler Rough-in | 4/10/2017 | 4/11/2017 | 4/11/2017 8:44:09 AM | A | PART |
|
|
Todays inspection was for the same area as previously inspected but for tenting. All tenting in this area is ok except one small spot. I discussed with Herb that prior to a cover inspection being given I need verification of insulation in the eaves to keep the sprinkler coverage with-in the 30' requirements and to verify insulation in the dog houses.
|
BLD17-00506
| FIRE-Final Inspection | 4/10/2017 | 4/11/2017 | 4/11/2017 8:41:41 AM | A | PASS |
|
|
Lifes safety passed. Owner to remove the non-functional/non-required emergency lights prior to a building inspection.
|