Inspections for the day of: Thursday, April 11, 2019.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01642 Final4/11/20194/11/20194/11/2019 3:02:29 PMPFAIL
Justin Phone #: ###-####
314.20- Boxes mounted in a combustible materials shall be flush with such materials or have an extension ring installed.
406.9(B)- Receptacles installed in wet locations shall be weather resistant type and have a in use cover identified as extra duty.
406.12- All 15 or 20 amp 120 volt receptacles installed in or on a residential building shall be tamper resistant type.
ELE19-00705 Temporary Service4/11/20194/11/20194/11/2019 2:17:58 PMPPASS
Temp Power inspection
Contact Toby Davis
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek t/s u/g n ok
ELE19-00549 Final4/11/20194/11/20194/11/2019 1:31:45 PMPFAIL
Final inspection please. Have a bless weekend. Phone #: ###-#### Inspection requested via web by Kyle Lott
Unit 904-
110.3- Devices shall be wired as per manufacturers instructions. 1st receptacle to left reverse polarity.
Unit 906-
300.15- All conduits and cables shall terminate in a box. EMT sticking up through floor with conductors capped off shall terminate in a box.
314.25- All boxes shall have covers Boxes along new demizing wall open boxes shall be covered.
ELE19-00825 Rough-In Permanent Service4/10/20194/11/20194/11/2019 10:01:40 AMAPASS
Most of this project to be done in EMT, needing cover. Please call Darryn ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Darryn Coburn
Service approved on previous inspection.
All required lighting and receptacles if not pre-installed in wall will be surface mount conduits and boxes. Circuits prewired in walls and ceiling rough in ok cover
ELE18-04780 Final4/10/20194/11/20194/11/2019 9:08:43 AMANH
There is a key on the panel at 1211 Melrose. If you have any questions please feel free to contact Jason ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
No access, only 1 key on top of 1211 panel and none on 1209. Key found did not work on 1209 doors,