ELE18-01642
| Final | 4/11/2019 | 4/11/2019 | 4/11/2019 3:02:29 PM | P | FAIL |
|
|
Justin Phone #: ###-#### 314.20- Boxes mounted in a combustible materials shall be flush with such materials or have an extension ring installed. 406.9(B)- Receptacles installed in wet locations shall be weather resistant type and have a in use cover identified as extra duty. 406.12- All 15 or 20 amp 120 volt receptacles installed in or on a residential building shall be tamper resistant type.
|
ELE19-00705
| Temporary Service | 4/11/2019 | 4/11/2019 | 4/11/2019 2:17:58 PM | P | PASS |
|
|
Temp Power inspection Contact Toby Davis Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek t/s u/g n ok
|
ELE19-00549
| Final | 4/11/2019 | 4/11/2019 | 4/11/2019 1:31:45 PM | P | FAIL |
|
|
Final inspection please. Have a bless weekend. Phone #: ###-#### Inspection requested via web by Kyle Lott Unit 904- 110.3- Devices shall be wired as per manufacturers instructions. 1st receptacle to left reverse polarity. Unit 906- 300.15- All conduits and cables shall terminate in a box. EMT sticking up through floor with conductors capped off shall terminate in a box. 314.25- All boxes shall have covers Boxes along new demizing wall open boxes shall be covered.
|
ELE19-00825
| Rough-In Permanent Service | 4/10/2019 | 4/11/2019 | 4/11/2019 10:01:40 AM | A | PASS |
|
|
Most of this project to be done in EMT, needing cover. Please call Darryn ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Darryn Coburn Service approved on previous inspection. All required lighting and receptacles if not pre-installed in wall will be surface mount conduits and boxes. Circuits prewired in walls and ceiling rough in ok cover
|
ELE18-04780
| Final | 4/10/2019 | 4/11/2019 | 4/11/2019 9:08:43 AM | A | NH |
|
|
There is a key on the panel at 1211 Melrose. If you have any questions please feel free to contact Jason ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan No access, only 1 key on top of 1211 panel and none on 1209. Key found did not work on 1209 doors,
|