Inspections for the day of: Thursday, April 11, 2019.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-04288 Final4/11/20194/11/20194/11/2019 1:47:56 PMPPASS
Phone #: ###-#### Inspection requested via web by Lucas Shaw
Final ok
ELE17-01863 Final4/11/20194/11/20194/11/2019 1:47:32 PMPPASS
Service change Final
Final ok
ELE18-04090 Final4/10/20194/11/20194/11/2019 11:34:50 AMAFAIL
access 1234, driveway will be cleared for access Phone #: ###-#### Inspection requested via web by David Nelson
As per 210.52 living spaces shall comply with wall spacing (room marked as storage has a condition heating and cooling sytem intall and as defined by IBC is livable as needs to be undre review
ELE19-01276 Electrical Rough-In4/10/20194/11/20194/11/2019 11:20:50 AMAPASS
ug for floor boxes, combo for lock is 1931 Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
U/G floor boxes
ELE17-00971 Final4/10/20194/11/20194/11/2019 10:47:49 AMAPASS
Call 1/2 hr prior to inspection###-####
Final ok Will also final permit for service change at this point
ELE19-01285 Electrical Rough-In4/10/20194/11/20194/11/2019 9:34:59 AMAPASS
Home is vacant. Lock box combo is 2730. Call with any questions. Phone #: ###-#### Inspection requested via web by Dylan Pierce Kitchen and basement re-wire ok to cover