MEC19-00533
| Final | 4/11/2019 | 4/11/2019 | 4/11/2019 3:32:09 PM | P | PASS |
|
|
Afternoon Inspection Please Phone #: ###-#### Inspection requested via web by Randy Hart
|
MEC19-01455
| Pressure Test | 4/10/2019 | 4/11/2019 | 4/11/2019 11:28:12 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige - 20lb gas pass for piping to furnaces and water heater in basement
|
MEC18-04702
| Final | 4/9/2019 | 4/11/2019 | 4/11/2019 10:31:44 AM | A | FAIL |
|
|
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 1) Need to label all fire damper access doors 2) Need to finish glueing and support condensate piping 3) Need UV protection on aramflex outdoors 4) Need to angle around fire damper openings in rated ceilings 5) Need to install missing exhaust fan grill 6) Need to extend dryer ducts outside of the wall 7) Need air balance report 8) Need to install A/C that was removed 9) Need letter from engineer for room usage change and removal of exhaust fan in oxygen storage
|
MEC19-00530
| Final | 4/10/2019 | 4/11/2019 | 4/11/2019 7:07:43 AM | A | CANC |
|
|
code 2468 Phone #: ###-#### >> Inspection requested via web by Randy Hart Inspection cancelled from web by: Randy Hart
|