Inspections for the day of: Thursday, April 11, 2019.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-00533 Final4/11/20194/11/20194/11/2019 3:32:09 PMPPASS
Afternoon Inspection Please Phone #: ###-#### Inspection requested via web by Randy Hart
MEC19-01455 Pressure Test4/10/20194/11/20194/11/2019 11:28:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Nicholas Paige - 20lb gas pass for piping to furnaces and water heater in basement
MEC18-04702 Final4/9/20194/11/20194/11/2019 10:31:44 AMAFAIL
Please call Bryan, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
1) Need to label all fire damper access doors
2) Need to finish glueing and support condensate piping
3) Need UV protection on aramflex outdoors
4) Need to angle around fire damper openings in rated ceilings
5) Need to install missing exhaust fan grill
6) Need to extend dryer ducts outside of the wall
7) Need air balance report
8) Need to install A/C that was removed
9) Need letter from engineer for room usage change and removal of exhaust fan in oxygen storage
MEC19-00530 Final4/10/20194/11/20194/11/2019 7:07:43 AMACANC
code 2468 Phone #: ###-#### >> Inspection requested via web by Randy Hart Inspection cancelled from web by: Randy Hart