FIR02-00085
| INSP-Final Inspection | 4/12/2002 | 4/12/2002 | 4/12/2002 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 409 On 4/12/2002 9:16:36 AM
|
BLD02-00187
| FIRE-Final Inspection | 4/10/2002 | 4/12/2002 | 4/12/2002 12:00:00 AM | A | PASS |
|
|
###-#### door at telecom room (in corridor) not installed; penetrations in all rated walls - Harold said he would have them ready for structural 4/12/2002 9:19:42 AM
|
FIR02-00081
| INSP-Sprinkler Rough-in | 4/12/2002 | 4/12/2002 | 4/12/2002 12:00:00 AM | P | FAIL |
|
|
Scott ###-#### soffits in kitchen/dining area are over 8 inches and will need pendants; laundry room soffits with heads too close to soffit; verify temp of furnace rooms may rewuire higher temp heads; draft stops require fire stopping; dry system not complete; need to complete wet system dry sidewall heads 4/12/2002 4:04:52 PM
|
FIR02-00118
| INSP-Supply line flush | 4/12/2002 | 4/12/2002 | 4/12/2002 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 04/12/2002 at 09:55:25. Contact: ###-####. underground cover only - okay 4/12/2002 4:02:02 PM
|
FIR02-00120
| INSP-Supply line flush | 4/12/2002 | 4/12/2002 | 4/12/2002 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 04/12/2002 at 09:56:17. Contact: ###-####. underground cover only - okay 4/12/2002 4:01:50 PM
|
FIR02-00123
| INSP-Supply line flush | 4/12/2002 | 4/12/2002 | 4/12/2002 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 04/12/2002 at 09:57:05. Contact: ###-####.
|