ELE03-02799
| Final | 4/12/2004 | 4/12/2004 | 4/12/2004 12:00:00 AM | A | NR |
|
|
suc
|
ELE04-00178
| Final | 4/12/2004 | 4/12/2004 | 4/12/2004 12:00:00 AM | A | NR |
|
|
suc
|
ELE04-00978
| Electrical Rough-In | 4/9/2004 | 4/12/2004 | 4/12/2004 12:00:00 AM | A | PASS |
|
|
warren; Phone #: ###-#### Internet Inspection Request from: Darla Downs
R/I Ok
service is not ready bonding is required in meter base and riser shall be made to be outside the building. 4/12/2004 9:55:44 AM
|
ELE04-01011
| Electrical Rough-In | 4/12/2004 | 4/12/2004 | 4/12/2004 12:00:00 AM | P | FAIL |
|
|
###-#### dan
no print on site.
258.148 and box overfilled in kitchen to the right of sink location
210.52 looks bad by kitchen sink,
parallel to frameing romex is within 1 1/4 in in several locations. 4/12/2004 3:10:32 PM
|
ELE03-03912
| Conference | 4/12/2004 | 4/12/2004 | 4/12/2004 12:00:00 AM | P | PART |
|
|
1:15 pm ###-#### hopkins 4/12/2004 9:56:42 AM
|
ELE04-01014
| Permanent Service | 4/12/2004 | 4/12/2004 | 4/12/2004 12:00:00 AM | P | PASS |
|
|
Please call prior to inspection///###-#### pat
P/S O/H N Ok 4/12/2004 3:25:48 PM
|
ELE04-00375
| Final | 4/12/2004 | 4/12/2004 | 4/12/2004 12:00:00 AM | P | FAIL |
|
|
LLOYD; Phone #: ###-#### Internet Inspection Request from: Darla Downs
receps not secure to the wall surface i n several locations
independent support wires not secured at both ends. 4/12/2004 2:26:43 PM
|
ELE04-01011
| Permanent Service | 4/12/2004 | 4/12/2004 | 4/12/2004 12:00:00 AM | P | PASS |
|
|
P/S U/g N Ok
|