Inspections for the day of: Monday, April 12, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-02799 Final4/12/20044/12/20044/12/2004 12:00:00 AMANR
suc
ELE04-00178 Final4/12/20044/12/20044/12/2004 12:00:00 AMANR
suc
ELE04-00978 Electrical Rough-In4/9/20044/12/20044/12/2004 12:00:00 AMAPASS
warren; Phone #: ###-#### Internet Inspection Request from: Darla Downs
R/I Ok
service is not ready bonding is required in meter base and riser shall be made to be outside the building. 4/12/2004 9:55:44 AM
ELE04-01011 Electrical Rough-In4/12/20044/12/20044/12/2004 12:00:00 AMPFAIL
###-#### dan
no print on site.
258.148 and box overfilled in kitchen to the right of sink location
210.52 looks bad by kitchen sink,
parallel to frameing romex is within 1 1/4 in in several locations. 4/12/2004 3:10:32 PM
ELE03-03912 Conference4/12/20044/12/20044/12/2004 12:00:00 AMPPART
1:15 pm ###-#### hopkins 4/12/2004 9:56:42 AM
ELE04-01014 Permanent Service4/12/20044/12/20044/12/2004 12:00:00 AMPPASS
Please call prior to inspection///###-#### pat
P/S O/H N Ok 4/12/2004 3:25:48 PM
ELE04-00375 Final4/12/20044/12/20044/12/2004 12:00:00 AMPFAIL
LLOYD; Phone #: ###-#### Internet Inspection Request from: Darla Downs
receps not secure to the wall surface i n several locations
independent support wires not secured at both ends. 4/12/2004 2:26:43 PM
ELE04-01011 Permanent Service4/12/20044/12/20044/12/2004 12:00:00 AMPPASS
P/S U/g N Ok