Inspections for the day of: Monday, April 12, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-02287 FIRE-Sprinkler Rough-in4/9/20044/12/20044/12/2004 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 4/9/2004 at 12:42:05 PM. Contact: ###-####. See sprinkler permit for details; okay to cover perimeter offices as shown on sprinkler plans 4/12/2004 10:30:46 AM
FIR04-00156 INSP-Sprinkler Rough-in4/12/20044/12/20044/12/2004 12:00:00 AMAPART
Not installed per plans and per Bill, Shilo will need to provide as-builts; okay to cover office at perimeter of building as identified on plans 4/12/2004 10:30:05 AM
BLD03-02893 FIRE-Conference4/9/20044/12/20044/12/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 4/9/2004 at 12:24:09 PM. Contact: ###-####. Met with John about need for submitting sprinkler plans 4/12/2004 2:56:20 PM
FIR03-00752 INSP-Conference4/9/20044/12/20044/12/2004 12:00:00 AMPPART
Ernie; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes met with john about sprinkler plans 4/12/2004 2:56:45 PM
BLD03-02543 FIRE-Conference4/9/20044/12/20044/12/2004 12:00:00 AMPPART
carl pence; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Met with owner about need for emergency lighting at second exit door from bar and in hallway to the south; extinguishers needed; 90 minute door must remain closed or have smoke detectors for release if on hold opens; occupant load sign; second door in hallway to exit is not to be locked - they may alarm door to prevent patrons from wandering back into storage area 4/12/2004 2:55:39 PM
FIR04-00108 INSP-Sprinkler Rough-in/Hydro4/12/20044/12/20044/12/2004 12:00:00 AMPPART
sam; Phone #: ###-#### Internet Inspection Request from: Darla Downs UG okay for cover - it is completed to UW connection; will need flush and hydro 4/12/2004 4:02:41 PM
FIR04-00083 INSP-Sprinkler Rough-in/Hydro4/12/20044/12/20044/12/2004 12:00:00 AMPNR
sam; Phone #: ###-#### Internet Inspection Request from: Darla Downs no work accomplished; not ready 4/12/2004 4:01:49 PM
FIR04-00096 INSP-Final Inspection4/12/20044/12/20044/12/2004 12:00:00 AMPFAIL
contact: Jim; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Calc'd for treatment room but there is not a door from hallway to treatment room; recalc 4/12/2004 3:40:57 PM