Inspections for the day of: Tuesday, April 12, 2005.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01752 FIRE-Final Inspection4/12/20054/12/20054/12/2005 4:01:11 PMPPASS
Fire life safety finaled, HVAC units shut down properly as required.
FIR05-00194 INSP-Final Inspection4/12/20054/12/20054/12/2005 3:21:57 PMPFAIL
Sprig-up EQ bracing must be installed to restrain lateral movement as per. NFPA 13 9.3.6.5.
BLD03-02949 FIRE-Final Inspection4/12/20054/12/20054/12/2005 1:20:22 PMPFAIL
chris ; Phone #: ###-#### Alarm tech. personel not available to facilitate testing of secured emergency door hardware at two required egress locations.
BLD04-02942 FIRE-Final Inspection4/12/20054/12/20054/12/2005 1:13:02 PMPPART
Temporary occupancy given per Dave Lokker, pending installation and testing of emergency lighting, and verification of door hardware.
BLD04-01048 FIRE-Final Inspection4/11/20054/12/20054/12/2005 11:53:51 AMAPASS
###-#### Robbie Fire alarm, life safety, and fire sprinkler finaled.
FIR05-00121 INSP-Sprinkler Rough-in/Hydro4/11/20054/12/20054/12/2005 11:01:06 AMAFAIL
Hydro. AG not ready for test, Rough in fail; need proper temp. heads in storage room, Upright in break room is too far below deck, Upright heads in office and open office are blocked by ductwork in some locations.
BLD04-01752 FIRE-Final Inspection4/11/20054/12/20054/12/2005 9:17:12 AMAFAIL
Fail inspection, HVAC units did not shut down immediately upon smoke test.