Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01263 Conference4/12/20064/12/20064/12/2006 3:45:14 PMPPART
OFF ###-#### CELL ###-#### - CRAIG
talked with contractor he will call if conference required
ELE06-00911 Electrical Rough-In4/11/20064/12/20064/12/2006 3:12:30 PMPPASS
Contact John Ostalosa.; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong r/i ok walls no ceiling needed
ELE06-00390 Final4/12/20064/12/20064/12/2006 2:24:47 PMPPASS
Please final Interchange Business monument sign Internet Inspection Request from: Radon Elaina sign ok has not been wired yet needs electrical contractor
ELE06-01136 Electrical Rough-In4/12/20064/12/20064/12/2006 1:58:21 PMPFAIL
Scheduled by a contractor via Hello! on 4/12/2006 at 7:47:21 AM. Contact: ###-####. corr. called 250.148 splice all eqiup grd in boxes,300.4 (A)(1)&(D) nail plates 11/4", 314.43 no screws or nails in plastic boxes, 314.17 replace all boxes with broken internal clamps,314.27(C) use listed floor box fam rm314.20 outside boxes shall be flush, 334.30&314.17(C) staple romex 12" or 8" of fixtures and boxes, 300.14 6" free length, 110.3(A) replace damaged box in fam rm by kit. upgrade permit for 7rms
ELE06-00974 Final4/11/20064/12/20064/12/2006 12:27:37 PMPFAIL
Please enter through gate on South side of home and through sliding glass door in rear.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas
corr. called 210.12 needs afci breaker for all circuits in bedrm
ELE05-04095 ELE-Aging Inspection4/12/20064/12/20064/12/2006 11:56:25 AM PART
called wsuc
ELE06-00603 Final4/11/20064/12/20064/12/2006 10:21:08 AMAPASS
Gary -- call 1st before insp; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok
ELE06-00125 Electrical Rough-In4/11/20064/12/20064/12/2006 9:39:33 AMAPASS
###-#### - dennis Note: pole bases ok
ELE06-00528 Final4/11/20064/12/20064/12/2006 9:15:11 AMAPASS
Scheduled by a contractor via Hello! on 4/11/2006 at 11:13:47 AM. Contact: ###-####. ok card signed
ELE06-01129 Electrical Rough-In4/11/20064/12/20064/12/2006 8:48:28 AMAPASS
jean; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/i 4 units ok p/s u/g new ok