FIR07-00156
| INSP-Alarm Testing | 4/11/2007 | 4/12/2007 | 4/12/2007 5:19:04 PM | P | PART |
|
|
Noted c/n items from the previous inspection have been completed, one additional SD at the hoistway to be installed when work on the second car is complete, final pending.
|
FIR07-00310
| INSP-Sprinkler Rough-in | 4/12/2007 | 4/12/2007 | 4/12/2007 5:15:11 PM | P | PASS |
|
|
Fire sprinkler permit work passed inspection.
|
BLD07-00793
| FIRE-Final Inspection | 4/12/2007 | 4/12/2007 | 4/12/2007 5:13:53 PM | P | FAIL |
|
|
Need to repair one exit sign/emergency light combo at the south exit.
|
FIR05-00753
| INSP-Alarm Testing | 4/11/2007 | 4/12/2007 | 4/12/2007 3:13:11 PM | A | PART |
|
|
Alarm testing completed for the existing portion of the TI only, expansion area not completed at this time, noted dB exceeds max allowable at the restrooms, notification and initiation tested okay, need receipt of signal verification, no items on the main FACP tested- partial test of tenant only, final pending related full building upgrade permit finals.
|
FIR05-00751
| INSP-Alarm Testing | 4/11/2007 | 4/12/2007 | 4/12/2007 3:07:21 PM | A | PART |
|
|
Alarm testing acceptable, noted shelving blocking one horn/strobe to be removed as discussed.
|
FIR07-00034
| INSP-Sprinkler Rough-in/Hydro | 4/11/2007 | 4/12/2007 | 4/12/2007 12:01:29 PM | A | PART |
|
|
OH rough-in for the second floor and basement are satisfactory, noted retaining straps at the beam clamps on the 2nd floor are not intended to be attatched to the ATR hangers, corrections in the basement are complete, riser is not yet finished, basement main as installed is 3", plan shows 21/2".
|
FIR06-00985
| INSP-Sprinkler Rough-in/Hydro | 4/11/2007 | 4/12/2007 | 4/12/2007 10:56:18 AM | A | NR |
|
|
Lacking water supply for line flush.
|