Inspections for the day of: Thursday, April 12, 2007.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00156 INSP-Alarm Testing4/11/20074/12/20074/12/2007 5:19:04 PMPPART
Noted c/n items from the previous inspection have been completed, one additional SD at the hoistway to be installed when work on the second car is complete, final pending.
FIR07-00310 INSP-Sprinkler Rough-in4/12/20074/12/20074/12/2007 5:15:11 PMPPASS
Fire sprinkler permit work passed inspection.
BLD07-00793 FIRE-Final Inspection4/12/20074/12/20074/12/2007 5:13:53 PMPFAIL
Need to repair one exit sign/emergency light combo at the south exit.
FIR05-00753 INSP-Alarm Testing4/11/20074/12/20074/12/2007 3:13:11 PMAPART
Alarm testing completed for the existing portion of the TI only, expansion area not completed at this time, noted dB exceeds max allowable at the restrooms, notification and initiation tested okay, need receipt of signal verification, no items on the main FACP tested- partial test of tenant only, final pending related full building upgrade permit finals.
FIR05-00751 INSP-Alarm Testing4/11/20074/12/20074/12/2007 3:07:21 PMAPART
Alarm testing acceptable, noted shelving blocking one horn/strobe to be removed as discussed.
FIR07-00034 INSP-Sprinkler Rough-in/Hydro4/11/20074/12/20074/12/2007 12:01:29 PMAPART
OH rough-in for the second floor and basement are satisfactory, noted retaining straps at the beam clamps on the 2nd floor are not intended to be attatched to the ATR hangers, corrections in the basement are complete, riser is not yet finished, basement main as installed is 3", plan shows 21/2".
FIR06-00985 INSP-Sprinkler Rough-in/Hydro4/11/20074/12/20074/12/2007 10:56:18 AMANR
Lacking water supply for line flush.