Inspections for the day of: Tuesday, April 12, 2011.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00149 INSP-Sprinkler Rough-in/Hydro4/12/20114/12/20114/12/2011 3:26:25 PMPPASS
An 8" lintel needs to be installed in the master shower area as discussed or a sprinkler pendant added. Also sprinkler pendants are located too close to one another in the living room area and will need to be relocated. These items can be verified at the final inspection. Sprinkler piping can be covered.
FIR11-00152 INSP-Conference4/12/20114/12/20114/12/2011 3:23:24 PMPPASS
Inspection was to verify the automatic operation of the temporary controller.
BLD10-02915 FIRE-Final Inspection4/11/20114/12/20114/12/2011 12:37:01 PMAFAIL
Provide for final inspection for BLD11-00265. Provide for testing of the exit discharge lights and exit signs. Repair emergency light in "check out" area. Provide single action hardware for the west exterior exit doors (per the plans one door panel is to be fixed). The "Cylinder Closet" exterior wall venting does not meet the height requirements of IFC 3006.2.1. Provide the NFPA Hazard Warning Sign per IFC 2703.5. Door is missing the smoke seal.
BLD11-00375 FIRE-Conference4/11/20114/12/20114/12/2011 11:46:18 AMADONE
Darren and I discussed storage arrangements.
BLD11-00700 FIRE-Final Inspection4/11/20114/12/20114/12/2011 10:22:17 AMAFAIL
Provide fire extinguishers as discussed, provide single action hardware on the warehouse doors per plans, cover the exposed electrical box. Remove the ware house racking that exceeds 8' or contact plan review for permitting.
BLD11-00159 FIRE-Final Inspection4/11/20114/12/20114/12/2011 8:15:34 AMAPASS
life safety passed