Inspections for the day of: Thursday, April 12, 2012.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00344 FIR-Aging Inspection4/12/20124/12/20124/20/2012 8:34:02 AM NR
Left voice mail for Dave with ADT requesting the project status.
FIR11-00472 FIR-Aging Inspection4/12/20124/12/20124/20/2012 8:33:45 AM NR
Left voice mail for Dave with ADT requesting the project status.
FIR12-00161 INSP-Sprinkler Rough-in4/11/20124/12/20124/12/2012 3:27:10 PMPPASS
See the city approved plans for additional areas where the sprinkler piping can be covered. Per fire sprinkler plan reviewer (Tim Frost) the sprinkler heads in the garbage chute at the fourth and second floors are OK. I noted over spaced heads in the first floor electrical room and a missing 4" control valve in the east side standpipe.
FIR12-00132 INSP-Final Inspection4/12/20124/12/20124/12/2012 3:18:25 PMPFAIL
No testing was performed due to various issues such as no water for the sprinkler system, electric alarm bell not mounted and pull station mounted too high.
FIR12-00118 INSP-Final Inspection4/11/20124/12/20124/12/2012 3:16:54 PMAFAIL
Tried to test the system but found that signals that appeared at the panel were not the same that central station received. Also as-builts still were not provided showing the remote annunciator. A re-inspection fee has been applied.
BLD11-01192 FIRE-Final Inspection4/10/20124/12/20124/12/2012 3:03:07 PMPFAIL
(1) The vehicle protection "bollards", required per the IFC do not meet section 312.2, 1, 2 and 5 for spacing between posts, filled with concrete or 3'-0" clearance from the propane tank. (2) The LOX tank has not been installed to verify the 5'-0" clearance from the property line. (3) Provide fire dept access signage per review note #8 (4) Finish mounting the fire extinguishers. (5) Provide the missing exits signs and repair the exit discharge and interior emergency lights. (6) Mount and test the fire sprinkler exterior alarm bell (7) The fire alarm system manual pull station is mounted too high and needs to be lowered. (8) United Water has not turned on the water supply for the fire sprinkler system therefore the forward flush could not be performed or any alarms for flow tested. (9) Repair the 6" sprinkler hanger at the top of the dry pipe system that has been disconnected. There may be other items added to the list once actual testing can be performed. Per the drawings and the electrical contractor the electrical service is less than the 1,200 ampers therefore panic hardware is not required on the electrical room.
FIR12-00084 INSP-Final Inspection4/11/20124/12/20124/12/2012 10:20:27 AMAPASS
Permit finaled
BLD12-00658 FIRE-Final Inspection4/11/20124/12/20124/12/2012 10:19:48 AMAPASS
Life safety passed