ELE12-00764
| Extend Permit 180 days | 4/12/2013 | 4/12/2013 | 4/12/2013 2:31:44 PM | P | PASS |
|
|
darlene - call prior to going Phone #: ###-#### talked to owner, ok extend permit
|
ELE10-00628
| ELE-Aging Inspection | 4/12/2013 | 4/12/2013 | 4/12/2013 2:30:47 PM | | DONE |
|
|
still under construction
|
ESC12-00852
| Aging Inspection | 4/12/2013 | 4/12/2013 | 4/12/2013 2:29:45 PM | | DONE |
|
|
looked ok
|
ESC12-00866
| Aging Inspection | 4/12/2013 | 4/12/2013 | 4/12/2013 2:28:35 PM | | DONE |
|
|
looked ok
|
ELE13-00562
| Electrical Rough-In | 4/12/2013 | 4/12/2013 | 4/12/2013 2:28:00 PM | P | PART |
|
|
ceiling inspection contact is keith ###-#### Phone #: ###-#### >> Inspection requested via web by JENNY EMEL front 1/2 ceiling only ok cover
|
ELE13-00876
| Temporary Service | 4/11/2013 | 4/12/2013 | 4/12/2013 2:14:59 PM | A | PASS |
|
|
THANKS Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE13-00376
| Final | 4/12/2013 | 4/12/2013 | 4/12/2013 1:24:49 PM | P | PASS |
|
|
justin Phone #: ###-#### ok final
|
ELE10-01244
| Final | 4/11/2013 | 4/12/2013 | 4/12/2013 12:24:59 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Louis Keller ok final
|
ELE13-00698
| Final | 4/11/2013 | 4/12/2013 | 4/12/2013 10:33:34 AM | A | FAIL |
|
|
call corey with questions thanks Phone #: ###-#### >> Inspection requested via web by Don Lustig called, BCC no violations shall be retained, shall follow NEC requirements, all outlets shall work (upstairs offices), shall provide gfci for outlets within 6' of sink, shall provide water heater disconnect, shall provide complete panel schedule, shall verify receptacle within 25 of a/c on roof, shall verify showroom receptacles, shall recall for inspection
|
ELE13-00843
| Rough-In Permanent Service | 4/8/2013 | 4/12/2013 | 4/12/2013 9:32:14 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk ri ok, p/s u/g n ok
|
ELE13-00873
| Rough-In Permanent Service | 4/11/2013 | 4/12/2013 | 4/12/2013 8:51:35 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman ri ok, p/s ug n ok
|
ELE13-00301
| Electrical Rough-In | 4/11/2013 | 4/12/2013 | 4/12/2013 8:03:05 AM | A | PASS |
|
|
Ceiling - Mike Phone #: ###-#### corrections made, ok cover ceiling only
|