Inspections for the day of: Tuesday, April 12, 2016.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00108 INSP-Sprinkler Rough-in4/12/20164/12/20164/14/2016 12:36:44 PMPCANC
Please call when you are heading out. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR16-00183 INSP-Sprinkler Rough-in/Hydro4/12/20164/12/20164/12/2016 2:45:08 PMPPASS
Under ground supply piping is ok to cover from the building to the new PIV. United water installed 4" supply piping instead of the 6" shown. I also spoke to the electrian about providing conduit for the PIV tamper switch.
BLD15-04346 FIRE-Conference4/12/20164/12/20164/12/2016 2:36:49 PMADONE
I spoke to the project superintendant about the NFPA 20 requirements for pitched floors, floor drains, emergency lighting and ventilation.
BLD15-02842 FIRE-Conference4/12/20164/12/20164/12/2016 12:49:38 PMADONE
Please call Barry 1 hr before arrival Phone #: ###-#### Inspection requested via web by Dennis Harmon
BLD16-01085 FIRE-Final Inspection4/11/20164/12/20164/12/2016 10:00:05 AMAPASS
Life safety passed