BLD15-03428
| FIRE-Final Inspection | 4/11/2016 | 4/12/2016 | 4/12/2016 1:57:40 PM | P | FAIL |
|
|
Signage reading "Door to remain unlocked when building is occupied" needs to be installed at main entry. The main entry has a double keyed deadbolt assembly installed, this deadbolt is going to remain, the northeast exterior exit door also has double keyed deadbolt, this door needs single action door hardware installed, one double keyed deadbolt is allowed. CO2 tank located in the storage room of building needs to be in place and secured from possible tipping before next inspection. Provide small documentation that is associated with city approved drawings at next inspection.
|
FIR15-00806
| INSP-Sprinkler Rough-in | 4/12/2016 | 4/12/2016 | 4/12/2016 1:18:39 PM | P | PART |
|
|
First floor rough to cover inspection complete, first floor approved for cover.
|
FIR15-00806
| INSP-Sprinkler Rough-in/Hydro | 4/12/2016 | 4/12/2016 | 4/12/2016 1:17:31 PM | P | PART |
|
|
Hydrostatic test complete for first floor overhead fire sprinkler piping.
|
BLD16-00354
| FIRE-Final Inspection | 4/11/2016 | 4/12/2016 | 4/12/2016 10:18:24 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, discussed location for fire extinguisher, fire extinguisher has current inspection tag. Final life fire safety inspection passed/complete.
|
FIR15-00602
| INSP-Supply line flush | 4/8/2016 | 4/12/2016 | 4/12/2016 10:03:46 AM | A | PART |
|
|
Southwest side underground supply flush complete, northwest underground supply will flushed at a later date.
|