Inspections for the day of: Wednesday, April 12, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01429 ELE-Aging Inspection4/12/20174/12/20174/18/2017 3:02:34 PM PASS
Still under construction
ELE12-02998 ELE-Aging Inspection4/12/20174/12/20174/18/2017 2:55:20 PM PASS
Waiting on contractor
ELE17-00115 Electrical Rough-In4/12/20174/12/20174/12/2017 3:25:32 PMPPASS
Ceiling Rough In inspection for Moffatt Thomas
Contact Jon Novak
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Grid rough in ok cover
ELE17-00938 Electrical Rough-In4/11/20174/12/20174/12/2017 3:15:27 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Area lighting being added. Supplied from restrooms to south 2 1" PVC conduits to pole lights at entrance to new area and several bollards thru out. East portion of underground rough in ok cover
ELE17-00975 Electrical Rough-In4/12/20174/12/20174/12/2017 1:50:02 PMPPASS
Kitchen remodel Rough in ok cover
ELE17-00034 Electrical Rough-In4/11/20174/12/20174/12/2017 12:55:08 PMAPASS
Phone #: ###-#### Inspection requested via web by CHRIS CARMINE
Underground on interior of shop rough in ok cover
MIS17-00112 ELE-Conference4/12/20174/12/20174/12/2017 12:40:54 PMPDONE
327 onsite to inspect detached building in rear of lot. Went to door for permission to access lot and owner escorted me thru house and noticed kitchen remodel of replacement of cabinets with some new wiring. Asked who performed work and he stated he did. I informed a permit is required and if he pulled 1 today additional fees would not be assessed. Answered all owners questions and at end of conversation he stated he would not pull permit if wall cover needed to be removed or if receptacles were required to be installed in tile backsplash. Wife would refuse these locations. 327 then created MIS and call 363 who is assigned to area.
ELE17-00994 Final4/11/20174/12/20174/12/2017 10:40:22 AMANR
Paul Phone #: ###-####
Power not connected yet.
ELE17-00994 Permanent Service4/12/20174/12/20174/12/2017 10:40:02 AMPPASS
Paul Phone #: ###-####
p/s o/h n ok
ELE16-03138 Final4/11/20174/12/20174/12/2017 9:56:14 AMANR
Tony Phone #: ###-####
Work yet to finish. See RI notes
ELE16-03138 Electrical Rough-In4/11/20174/12/20174/12/2017 9:55:27 AMAFAIL
Juile ###-#### Tony Phone #: ###-####
Homeowner requested inspections.
All-star Electric has open permit ###-####.
Electrical contractor only one to request inspections under permit purchased.
210.52- Door to be framed in at entrance to bedroom shall have a receptacle outlet located with in 6'. No point measured along floor line shall be greater than 6' fram a receptacle outlet.
300.15- All wiring shall terminate in a box with cover. Old AC location next to stairway outdoors and misc covers needed inside.
400.8- Flexible cords shall not pass thru doorway, walls, or ceiling. Relocate sump pump receptacle to inside room.
410.16- Luminaires located in closets and storage area shelves shall be totally enclosed type. New closet to be built in bed with 2 cans with open type and open lamp in storage area.
422.30- Water heater shall have a disconnecting means located with in sight. Lock out acceptable as per 110.25.