Inspections for the day of: Thursday, April 12, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01403 Conference4/12/20184/12/20184/12/2018 2:29:19 PMPDONE
Contact: Dave Phone #: ###-#### Inspection requested via web by Harvey Reyna
Discussed location of panels, what wiring ok to remain, show window receptacles, inspections needed.
240.24(C)- Panel location in kitchen area shall have adequate distance from sink for a barrier providing separation.
240.24(E)- Panel located in bathroom may remain if enclosed with walls and a doorway creating separation. Also noted in BCC 4-05-31(A).
210.62- Show window receptacles shall be located with in 18" of top of window and spacing corrected.
400.12- Asked if existing light fixtures could remain. Flexible cords shall not be used as substitute for structural wiring. Lighting shall comply with IECC for total wattage allowed.
Asked if could request a inspection for certain areas to be done in phases to help job move forward quicker. OK to request couple extra inspections.
ELE18-00463 Final4/10/20184/12/20184/12/2018 1:23:19 PMAPASS
Pls contact Barry (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes
Final ok
ELE18-00573 Permanent Service4/10/20184/12/20184/12/2018 1:21:07 PMAPASS
Pls contact Barry (Electrician) one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes p/s o/h rec ok
ELE18-00573 Final4/12/20184/12/20184/12/2018 1:20:47 PMPPASS
Pls contact Barry (Electrician) one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes Final ok
ELE18-00899 Final4/12/20184/12/20184/12/2018 10:28:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Mark M
Final ok
ELE18-01195 Electrical Rough-In4/11/20184/12/20184/12/2018 9:54:31 AMAPASS
Wall cover please. Phone #: ###-#### Inspection requested via web by Kyle Lott
Wall rough in ok cover
ELE18-01278 Rough-In Permanent Service4/11/20184/12/20184/12/2018 9:21:44 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
Rough in ok cover p/s u/g n ok
ELE18-01279 Rough-In Permanent Service4/11/20184/12/20184/12/2018 8:52:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall
Rough in ok cover p/s u/g n ok